The GPD-515-G5-Braking-Connections from Yaskawa is a dynamic braking module designed to enhance the performance of drive systems. It incorporates a transistor unit along with a remote resistor to manage braking effectively.

Call for an immediate quote
2 Year DO Supply Warranty
Available
Ships from Raleigh, NC
Not an Authorized Distributor: DO Supply is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All of our products come with DO Supply's 2-year warranty.
Learn more

Technical specifications for GPD-515-G5-Braking-Connections

ManufacturerYaskawa
Product TypeDynamic Braking Module
Product LineGPD
Part NumberGPD-515-G5-Braking-Connections
Brake ComponentsTransistor Unit & Remote Resistor
Cable LengthMax 10 m between units
Clearance (Transistor)30 mm sides, 100 mm top/bottom
Clearance (Resistor)50 mm sides, 200 mm top
Voltage RatingMatch DC bus voltage
L1-L3 TerminalsMain AC input unaffected
Connect TerminalsB, P, Po, N per wiring drawing
Terminal ScrewsM4 (signal), M5 (power)
Cable Size12–10 AWG for power, 18–14 AWG for signal
GroundingEnclosures ≤100 Ω to chassis ground
ShieldingSeparately group noisy power leads
SafetyPower off & DC bus discharge before wiring
Test Megger900 V insulation test after install

The Yaskawa GPD-515-G5-Braking-Connections module serves as a dynamic braking solution for varying applications. Designed with operational efficiency in mind, it features a combination of a transistor unit and a remote resistor. For optimal cable installation, the maximum distance between units should not exceed 10 meters. The module requires specific clearances, including 30 mm on the sides and 100 mm for the top and bottom of the transistor, while the resistor necessitates 50 mm of clearance on the sides and 200 mm on top to maintain efficient operation.

It is crucial that the voltage rating matches the DC bus voltage for proper functionality. Meanwhile, the L1-L3 terminals remain unaffected by the main AC input, allowing for seamless connections. Connection terminals are designated as B, P, Po, and N, allowing users to follow the specific wiring drawing provided. Additionally, the terminal screws feature sizes of M4 for signal connections and M5 for power connections.

The module also stipulates cable requirements: use 12–10 AWG for power cabling and 18–14 AWG for signal conductors. Grounding enclosures should maintain a resistance of 100 Ω or less to the chassis for safety. To mitigate electrical noise, it is recommended to shield and group noisy power leads separately. Safety precautions include powering off the system and discharging the DC bus before any wiring work is conducted. Lastly, after installation, a megger insulation test at 900 volts must be performed to verify installation integrity.