1746-HSCE2

|

The Allen-Bradley 1746-HSCE2 is an SLC 500 input module. This is a multi-channel High-speed counter module. This is an intelligent module that is capable of counting in both directions. It has inputs ±A1, ±B1, ±Z1, ±A2, ±B2, and ±Z2 with input voltage range of 4.2V dc to 12V dc and 10V dc to 30V dc. It also has Eight (8) outputs composed of Four (4) virtual and Four (4) real 5-30 VDC sourcing outputs.

Ships Mon, May 19.
In Stock
Ships from Raleigh, NC
2 Year DO Supply Warranty
Not an Authorized Distributor: DO Supply is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with DO Supply's 2-year warranty.
Learn more
  • We sell industrial automation parts backed by our 2-year DO Supply Warranty.

  • Same-day domestic and expedited international shipping with UPS, FedEx, DHL, and more.

  • AMEX, Visa, MasterCard, Discover, wire transfer, and more, plus flexible payment plans.

  • Repair and exchange services for all existing automation products.

  • Reseller Options

    Drop shipping, blind shipping, and account shipping with no extra fees.

Technical specifications for 1746-HSCE2

ManufacturerRockwell Automation
Module TypeHigh-Speed input module
SeriesSLC 500
Part Number/Catalog No.1746-HSCE2
BrandAllen-Bradley
Module inputs:±A1, ±B1, ±Z1, ±A2, ±B2, and ±Z2
Input Voltage, nominal5VDC; 24VDC
Operating Voltage Range4.2V dc to 12V dc; 10V dc to 30V dc
Min. Pulse Width475 ns
Min. Phase Separation200 ns
Max. Input Frequency1 MHz
Module outputs:Eight (8) outputs; Four (4) Virtual / Four (8) real
Output voltage range:10-30 VDC
Inputs4 Single-Ended and 2 Differential Quadrature
Outputs4
Input Frequency1 Megahertz
Backplane Current (5 Volts)250 milliamps
Update Time1.5 milliseconds
Slots1
I/O Connection1746-RT25G
Step Response100 milliseconds in, 2.5 milliseconds out
Input Voltage30 Volts DC
UPC10611320083757
Rockwell Disclaimer: The product is used surplus. DO Supply is not an authorized surplus dealer or affiliate for the Manufacturer of this product. The product may have older date codes or be an older series than that available direct from the factory or authorized dealers. Because DO Supply is not an authorized distributor of this product, the Original Manufacturer's warranty does not apply. While many Allen-Bradley PLC products will have firmware already installed, DO Supply makes no representation as to whether a PLC product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. DO Supply also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Rockwell, its distributors, or any other source. DO Supply also makes no representations as to your right to install any such firmware on the product. DO Supply will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

The 1756-HSCE2 is a multi-channel High-speed counter module. This module is an intelligent module, used for specific purposes of counting, totalizing, position monitoring and other high-speed applications. This module comes with ±A1, ±B1, ±Z1, ±A2, ±B2, and ±Z2 with input voltage range of 4.2VDC to 12VDC and 10VDC to 30VDC. It is also provided with Eight (8) outputs that is comprised of Four (4) virtual and Four (4) real 5-30 VDC sourcing outputs.

The input channels of this module accepts signals with minimum pulse width of 475 ns with minimum pulse separation of 200 ns and maximum input frequency of 1 MHz. This module has backplane isolation of 1000V and channel to output isolation of 500V. Each channel of the module has an input voltage range of 4.2V dc to 12V dc when operated at 5VDC and 10V dc to 30V dc when operated at 24VDC.

The module’s output specifications include an output voltage range of 5-30 VDC with maximum On-state output current per channel of 1.0 A while the Max. On-State Current per module is 2.0 A at 40°C and 1.5 A at 60°C. The maximum On-state voltage drop is 0.5V and Maximum Off-State Leakage Current of 100 µA. The 1746-HSCES has backplane isolation of 1000V and output to input isolation of 500V.

This module can be configured to perform counting on both directions. It supports up to Four (4) pulse counters or Two (2) quadrature counters. Each module counter is capable of counting up to +/- 8,388,607, configured as linear or ring counter. This counter module has a dedicated processor to process signals. It can be used in the entire SLC 500 system and with the 1747-ASB SLC Remote I/O Adapter (RIO) Module as a RIO component.

The input channels A and B are configurable to count single-ended pulse for up to 4 input devices. The module features a capacity to control adjustments when actively counting pulses. This allows for greater reliability. The Z input channel handles the storing, holding, and resetting of the counter data. When using a low-frequency input signal, the 1746-HSCE2 may accept false pulses. To avoid high-frequency noise on low-frequency signals, the user should remove the noise with the 1746-HSCE2 input cable to lead the current away from noise sources.

In case of short circuit or overloaded current, the 1746-HSCE2 has a protection that is thermal cut-out based. This serves as a limit that will turn off all channels within milliseconds when the thermal cut-out temperature is reached. The 1746-HSCE2 is compatible with all SLC 500 CPU modules. The counter capability extends to 24 bits (±8,388,607) with operating class 1 or 4. The input voltage ranges from 4.2 to 30 Volts DC and output current to 1 Ampere. Input frequency response reaches to 1 M Hz and 0.7 to 1.6 milliseconds back-plane response time. It is a self-determined rate of periods with no sequence mode and has 16 ranges to count/rate modes. The controller has a 1 preset input for Counters 1 and 2 only but no preset input for Counters 3 and 4. The controller’s isolation voltage is tested to withstand at 1000 Volts. The back-place current at 5 Volts is 250 mA and 0 mA at 24 Volts with a typical throughput of 700 µs. It also has a maximum and minimum thermal dissipation of 1.25 Watts.

Revision Part #Also known as
1746-HSCE2 Ser A1746-HSCE2/A, Series A, Rev A