Free UPS Ground on All Orders!
+1 (919) 205-4392
Allen Bradley SLC 500 1746-NI16I

Product image is representative; revision or series may vary. Contact us to request a specific version.

1746-NI16I

|

The Allen-Bradley 1746-NI16I is a SLC 500 Analog I/O Module. This Analog I/O Module has Sixteen (16) Inputs configurable for 0 to 20 mA, 4 to 20 mA, ±20 mA, and 0 to 1 mA. This module is a single-slot module.

In Stock
Ships from Raleigh, NC
2 Year DO Supply Warranty
Not an Authorized Distributor: DO Supply is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All of our products come with DO Supply's 2-year warranty.
Learn more
Rockwell Disclaimer: The product is used surplus. DO Supply is not an authorized surplus dealer or affiliate for the Manufacturer of this product. The product may have older date codes or be an older series than that available direct from the factory or authorized dealers. Because DO Supply is not an authorized distributor of this product, the Original Manufacturer's warranty does not apply. While many Allen-Bradley PLC products will have firmware already installed, DO Supply makes no representation as to whether a PLC product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. DO Supply also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Rockwell, its distributors, or any other source. DO Supply also makes no representations as to your right to install any such firmware on the product. DO Supply will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Technical specifications for 1746-NI16I

ManufacturerAllen Bradley
CategoryPLCs
Product LineSLC 500
Part Number1746-NI16I
GTIN10611320228196
Weight0.75 lbs (0.34 kg)
Module TypeAnalog I/O Module
Backplane Current (5 Volts)125 milliamps
InputsSixteen (16)
Backplane Current (24 Volts DC)75 milliamps
Electrical Signal type0 to 20 mA, 4 to 20 mA, ±20 mA, and 0 to 1 mA
Bandwidth6-250 Hertz
Chassis locationAny I/O module slot except slot 0
Step Response9-630 milliseconds
Backplane Current(5 Volts) 125 mA;(24 Volts DC)75 mA
Thermal Dissipation2.43 Watts
Conversion typeSigma - Delta
ApplicationsCombination 120 Volts AC I/O
Input FilteringLow-pass digital filter with programmable filter frequencies
UPC10611320228196
Input Filter Frequencies6 Hz, 10 Hz, 20 Hz, 40 Hz, 60 Hz, 80 Hz, 100 Hz, 250 Hz
Isolation500V ac isolation for 1 second
LED Indicators5 green status indicators one for each group of 4 channels, and one for module status
Recommended CableBelden #8761 or equivalent

The Allen Bradley 1746-NI16I is an Analog Input Module, with 16-bit resolution and 16 input channels. This module falls into a Voltage Category of -20 to 20 mA. Its backplane current at 5 Volts is 125 mA, while 24 Volts results in 75 mA. Its backplane power consumption is 2.425 Watts maximum (0.625 Watts at 5 Volts DC and 1.8 Watts at 24 Volts DC). The common mode voltage range of this module is +/-10.25 Volts relative to the analog common terminal.

This unit has a relative humidity of 5% to 95% without condensation. Its operating temperature range is -25 to 60 degrees Celsius (-13 to 140 degrees Fahrenheit) while its nonoperating temperature lies between -40 and 85 degrees Celsius (-40 and 185 degrees Fahrenheit). Its Input impedance is 249; its maximum voltage input is ±8 Volts between analog common and any input terminal, and the maximum current input is ±30 mA. The thermal dissipation of this module is 2.43 Watts, and the AIFM Connector of this module is 25-pin D-shell. When installing modules in the chassis, it is not necessary to remove the terminal blocks from the module. However, if the terminal block is removed, use the label located next to the terminal block to identify the location and type of module.

Analog inputs are used to interface analog process variables to measure its magnitude. It is primarily used to monitor or used as feedback signal for closed loop control systems to implement manual or automatic control with the use of control methods typically Proportional-Integral-Derivative (PID) algorithm. Without this feedback signal, automatic control cannot be fully implemented.

Other parameters may also be defined to fine tune the module’s operation. It has a user selectable Data Format that such as Engineering Units, Scaled for PID, Proportional Counts with -32,768 to +32,767 range and Proportional Counts with User-Defined Range, Class 3 only. This module also features capability of detecting an open circuit with reference to the input channel. The module’s time to actuate is less than 5 Seconds. When wiring signals to the module, recommended cable is Belden #8761 or any equivalent may be used. Use a maximum wire size of 14 AWG. Up to Two (2) wires may be terminated per terminal. These are recommended to avoid cluttering and difficulty to close the module door.

This High-Resolution Analog Input module has 5 green status indicators one for each group of 4 channels, and one for module status to provide visual indication regarding the module’s state and channel operation.

Revision Part #Also known as
1746-NI16I Ser A1746-NI16I/A, Series A, Rev A
Don't see your particular revision? Contact us now.