Free UPS Ground on All Orders!
+1 (919) 205-4392
Allen Bradley SLC 500 1746-P3
Not an Authorized Distributor: DO Supply is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with DO Supply's 2-year warranty.
Learn more

1746-P3

|

The Allen-Bradley 1746-P3 is a SLC 500 Power Supply. This is a Power Supply operates at an input supply range of 19.2 - 28.8 VDC. It has an internal current capacity of 3.6 A at 5VDC 0.87 A at 24VDC. It supplies power to the backplane which is used to energize the SLC 500 modules attached to the chassis.

Ships Mon, May 19.
In Stock
Ships from Raleigh, NC
2 Year DO Supply Warranty
Not an Authorized Distributor: DO Supply is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All our products come with DO Supply's 2-year warranty.
Learn more
  • We sell industrial automation parts backed by our 2-year DO Supply Warranty.

  • Same-day domestic and expedited international shipping with UPS, FedEx, DHL, and more.

  • AMEX, Visa, MasterCard, Discover, wire transfer, and more, plus flexible payment plans.

  • Repair and exchange services for all existing automation products.

  • Reseller Options

    Drop shipping, blind shipping, and account shipping with no extra fees.

Technical specifications for 1746-P3

ManufacturerRockwell Automation
Location1746 Chassis, Left Side
Input Voltage Range19.2-28.8 VDC
Module TypePower Supply
SeriesSLC 500
Part Number/Catalog No.1746-P3
BrandAllen-Bradley
Nom Input Voltage24VDC
Typical line power requirement90 VA
Inrush Current20 A
Isolation Voltage600V ac RMS for 1 s (version B or later)
Current Capacity3.6 A at 5V dc and 0.87 A at 24V dc
Hold Up time5 ms (full load); 1000 ms (no load)
Fuse protection1746-F3 or equivalent
Temperature, ambient operating0...60 °C (32...140 °F)
Current capacity deration5% above 55 °C (131 °F).
Input Voltage24 Volts DC
Input Power61 Watts
Backplane Current (5 Volts)3.6 Amps
Backplane Current (24 Volts)0.87 Amps
FrequencyDC
Weight2.5 pounds (1.1 kilograms)
Dimensions5.5 x 2.9 x 5.7 inches
Operating Temperature0 to 60 degrees Celsius
UPC10662073521430
Rockwell Disclaimer: The product is used surplus. DO Supply is not an authorized surplus dealer or affiliate for the Manufacturer of this product. The product may have older date codes or be an older series than that available direct from the factory or authorized dealers. Because DO Supply is not an authorized distributor of this product, the Original Manufacturer's warranty does not apply. While many Allen-Bradley PLC products will have firmware already installed, DO Supply makes no representation as to whether a PLC product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. DO Supply also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Rockwell, its distributors, or any other source. DO Supply also makes no representations as to your right to install any such firmware on the product. DO Supply will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

The 1746-P3 is a Power Supply module. This module is part of the SLC 500 controller platform that is mainly used to provide power to the 1746 backplane to which the SLC 500 modules are attached to. This power supply module is located at the left-most area of the rack and does not occupy a chassis slot. It internally converts input power to a voltage level usable by the modules, specifically, converts an input supply voltage of 19.2...28.8V dc to an internal supply of 3.6 A at 5V dc and 0.87 A at 24V dc.

The 1746-P3 is especially applicable to the SLC 500 Modular control system. It has a typical line power requirement of 90 VA with isolation of 600V ac RMS for 1 second. This module features a pre-installed fuse which may be replaced with Allen-Bradley recommended 1746-F3 or any equivalent. Additionally, Fuse sizes declared are used for end-devices only. It may be reduced depending on the size of circuit wiring. This power supply also exhibits a CPU hold-up time of 5 ms when operating at full load or 1000 ms when no load. This hold-up time allows the power supply to maintain the operating state of the CPU from the time when the supply voltage drops below the minimum range.

The 1746-P3 is certified by Underwriter’s Laboratories (UL), Listed as Industrial Control Equipment for Class 1, Division 2, Groups A, B, C, D Hazardous Locations; C-UL Listed as Industrial Control Equipment for Class 1, Division 2, Groups A, B, C, D Hazardous Locations as well as other standardization and certifying bodies.

The current capacity for the module is 3.6 Amps at 5 Volts DC and 0.87 Amps at 24 Volts DC. The fuse recommended for use with the 1746-P3 module is the Allen-Bradley 1746-F3 fuse (or an equivalent fuse including the BUSSMAN AGC 5 or the Nagasawa ULCS-61ML-5 fuse). There is no isolation between the backplane and input terminals. There is, however, a dielectric withstand between the chassis ground terminal and input terminals which is 600 Volts AC RMS for 1 second. The recommended ambient temperature range for the 1746-P3 module to operate at is from 32 to 140 degrees Fahrenheit. The hold-up time for the CPU is 5 milliseconds at a full load and 1000 milliseconds at no load. The dimensions of the 1746-P3 are 139.7 x 79.2 x 144.8 millimeters. The module is designed for use at altitudes of up to 2000 meters without derating. It should be used in Pollution Degree 2 rated environments and in applications rated at Category II. Only a 1/8 inch flat head and a 1/4 inch Phillips head screwdriver are required for the installation of the module. To protect the module against ESD, it should be kept in static-shield packaging when it is not in use, the connector pins and backplane connector should not be touched and touching the circuit components on the module should be avoided too.

Revision Part #Also known as
1746-P3 Ser A1746-P3/A, Series A, Rev A
Request a quote
Don't see your particular revision? Contact us now.

Testimonials

4.99 /5.0
Recommended
4.99 average / 907 reviews