Product image is representative; revision or series may vary. Contact us to request a specific version.
The S811T30N3S is part of Eaton’s non-combination IT soft starter. This device is part of the S811+ product family. It is a 3-pole motor controller with an input voltage range of 200 - 600 VAC and a control voltage of 24 VDC. It delivers an output current of 304 Amperes with an output power of 100 Horsepower at 200/208V 3PH; 100 Horsepower at 230/240V 3PH; 250 Horsepower at 460/480V 3PH and 300 Horsepower at 575/600V 3PH.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Eaton Cutler-Hammer |
|---|---|
| Product Type | Open Soft Starter |
| Product Line | S811 Soft Starters |
| Part Number | S811T30N3S |
| Weight | 150.00 lbs (68.04 kg) |
| Frame Size | 200 mm |
| Amps | 30 |
| Option | No |
| Operating Modes | Current limit start, Kick-start, ramp-start and ramp- stop |
| Features | Standard |
| Line Voltage | 200-600 VAC, 47 - 63 Hz |
| 230V ACHp Rating | 100 |
| Control Voltage | 24 VD |
| Max. Current Capacity | 304 |
| Output current | 304 Amperes |
| Insulating Voltage Ui | 660V AC |
| Output power | 100 Horsepower at 200/208V 3PH; 100 Horsepower at 230/240V 3PH; 250 Horsepower at 460/480V 3PH; 300 Horsepower at 575/600V 3PH |
| Operating Voltage | 200-600V AC |
| Output contacts | Class A and Class C |
| Operating Frequency | 47-63 Hz |
| Output contact voltage rating | 120 VAC / 240 VAC |
| Resistance to Shock | 15G |
| Output contact current rating | 3:00 AM |
| Bypass Mechanical Lifespan | 10M |
| Selectable Overload Trip Class | Trip Class 5, 10, 20 and 30 |
| Overload setting | 30-100% |
| Mounting | Panel Mount |
The S811T30N3S is a motor soft-starter that is manufactured by Cutler Hammer, a division of Eaton Corporation. This is a solid-state controller that can be used in a wide variety of applications such as starting and stopping motors that is one of the most common prime movers of machines or equipment in the industry. The S811T30N3S is designed to operate when supplied with 200 - 600 VAC voltages while the control circuitry of this soft-starter is rated at 24 VDC. The nominal output or load voltages of this soft-starter are 208/240/380/480/575 Volts AC with output current rating of 304 Amperes and ratings that varies depending on the load voltage particularly, 100 Horsepower at 200/208V 3PH; 100 Horsepower at 230/240V 3PH; 250 Horsepower at 460/480V 3PH and 300 Horsepower at 575/600V 3PH. The S811T30N3S comes with an integral bypass with a mechanical lifespan of 10 Million actuation, an insulating voltage of 660 V. In addition, this soft-starter is provided with a Class A and Class C relay contact output rated 240 VAC / 120 VDC and a current of 3 Amperes. This soft-starter is capable of implementing Current limit start, Kick-start, ramp-start, and ramp-stop. Adjustable ramp parameter time ranges from 0.5-180 seconds and 0.5-360 seconds for extended ramp function. The S811T30N3S has an open-type enclosure. It carries certifications from IEC 60947-4-2, EN 60947-4-2, UL, CE, CSA. Embedded motor protection includes an overload trip class of 5,10,20 and 30 with a configurable overload setting of 30-100%. This soft-starter can be operated at a shock rating not exceeding 15 g and vibration not exceeding 3g.
The Eaton Cutler-Hammer S811T30N3S motor starter is a reduced voltage solid-state motor starter. It can apply a 3-phase soft start in applications such as pump, rock crusher, wood-chipper, conveyor, compressor, and bread mixer applications. The S811T30N3S motor starter has a 200-millimeter frame size, and it belongs to the Eaton Intelligent Technology series of motor starters called the S811 series. The unit can be upgraded with MOVs (Metal Oxide Varistors or surge suppressors) that can be mounted on the line side or on the load side of the motor starter. The device can be positioned either horizontally or vertically, but there should be enough clearance (about 4 inches) around the soft starter for good air circulation. The Eaton S811T30N3S motor starter has a current rating of 304 Amps and it requires a 200 to 600 Volts AC 3-phase power supply. It can digitally send information over relay outputs. Relay 1 is a Form A normally-open contact that closes when the bypass contactor is powered. This signal remains closed until the soft-stop is initiated. Relay 2 is a Form C normally-open contact that is programmed to close when there is a fault condition. The S811T30N3S motor starter can be programmed to act in a certain way in the case of a trip situation. It can be adjusted to automatically reset the trip as soon as the trip condition is no longer present. The other option is to configure the device to work in the manual reset mode. In this case, the operator must press the RESET button on the control panel of the unit to clear an alarm. The digital inputs on the unit are 24 Volts DC rated.
Yes, the S811T30N3S includes a free 2-year DO Supply warranty. You can upgrade to a 3-year warranty at checkout for even more protection.
The S811T30N3S supports Current limit start, Kick-start, ramp-start and ramp-stop.
The S811T30N3S’s output power ratings are 100 Horsepower at 200/208V 3PH; 100 Horsepower at 230/240V 3PH; 250 Horsepower at 460/480V 3PH and 300 Horsepower at 575/600V 3PH.
The FLA of the S811T30N3S is 304 Amperes.
The S811T30N3S motor starter is a soft starter that has been designed and manufactured by Eaton Cutler-Hammer. It is part of the Eaton S811 soft starters series. The S811T30N3S soft starter has a mounting base for easy and secure mounting, DIP switches for easy configuration, network terminals for easy communication, and a digital interface module for easy application monitoring. It supports edge sensing control and level sensing control. The S811T30N3S soft starter can be started up with the voltage ramp start mode and the current limit start mode.