Product image is representative; revision or series may vary. Contact us to request a specific version.
The HJD3200W circuit breaker from Eaton Cutler-Hammer features a compact design optimized for thermal and magnetic protection. With a continuous current rating of 200 A, this unit is rated for AC voltages up to 600 VAC and DC voltages up to 250 VDC, allowing it to be applicable in various electrical setups.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Eaton Cutler-Hammer |
|---|---|
| Product Type | Thermal-Magnetic Molded-Case Circuit Breaker |
| Product Line | Series C Circuit Breakers |
| Part Number | HJD3200W |
| Weight | 12.50 lbs (5.67 kg) |
| UPC | 786679319208 |
| Current Rating | 200 A Continuous |
| Rated AC Voltage | Up to 600 VAC |
| Rated DC Voltage | Up to 250 VDC |
| Number of Poles | 3 Poles |
| Frame Size | J-Frame |
| Trip Adjustment | Fixed thermal and fixed magnetic settings |
| Interrupt Capacity at 240 VAC | 100 kAIC |
| Interrupt Capacity at 480 VAC | 65 kAIC |
| Interrupt Capacity at 600 VAC | 25 kAIC |
| Circuit Breaker Style | Complete Breaker Assembly |
| Connection Provision | Terminal Lugs Not Included |
| Mounting Style | Panel Mounted |
| Frequency Range | 50/60 Hz |
The Eaton Cutler-Hammer model HJD3200W is designed as a thermal-magnetic molded-case circuit breaker, ideal for a range of high-demand electrical applications. It supports a continuous current rating of 200 A and is capable of handling AC voltages reaching up to 600 VAC, alongside a DC voltage rating of up to 250 VDC. This flexibility makes it suitable for both commercial and industrial installations.
This circuit breaker operates with a J-frame size and features three poles, making it a suitable choice for three-phase systems. The trip settings are non-adjustable, as they are fixed for thermal and magnetic mechanisms, providing dependable protection without user intervention for adjustments.
In terms of safety and performance, this breaker boasts significant interrupt capacity, rated at 100 kAIC for a 240 VAC application, 65 kAIC at 480 VAC, and diminishing to 25 kAIC at the maximum 600 VAC. The unit is classified as a complete breaker assembly, ready for installation. It has a panel-mounted style for straightforward integration into electrical setups. Please note that terminal lugs are not provided with this model, so separate ordering may be necessary. With a frequency range operational between 50/60 Hz, the HJD3200W is engineered to provide lasting performance and safety in demanding electrical environments.