The RM7830A1029 from Honeywell is a relay control module suitable for on/off power burner applications. Its design supports a supply voltage of 120 VAC and operates within specified frequency limits.

Call for an immediate quote
2 Year DO Supply Warranty
Available
Ships from Raleigh, NC
Not an Authorized Distributor: DO Supply is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All of our products come with DO Supply's 2-year warranty.
Learn more

Technical specifications for RM7830A1029

ManufacturerHoneywell
Product TypeRelay Control Module
Product Line7800 Series
Part NumberRM7830A1029
Burner Application TypeOn/Off Power Burner
Pilot Flame Establishing Period3 seconds or 5 seconds
Main Flame Establishing Period3 seconds or 5 seconds
Supply Voltage120 VAC
Minimum Frequency50 Hz
Maximum Frequency60 Hz
Post-Purge Timing30 seconds
Early Spark TerminationYes, 5 seconds
Minimum Ambient Temperature-40°C
Maximum Ambient Temperature60 °C

Model RM7830A1029 from the Honeywell 7800 Series is engineered as a relay control module for burner systems. Weighing in at 1.81 lbs, it is tailored for on/off power burner applications. This model operates on a supply voltage of 120 VAC while ensuring efficient performance within a frequency range of 50 Hz to 60 Hz.

The burner control specifics include a configurable pilot flame establishment period of either 3 or 5 seconds, which can be matched by the main flame establishment period. Additionally, it incorporates post-purge timing lasting for 30 seconds to ensure safe operation post-ignition.

An early spark termination feature enhances safety protocols as it allows for spark end after 5 seconds if the flame is not established. In terms of environmental resilience, this module is designed to operate effectively between minimum and maximum ambient temperatures of -40°C and 60°C, respectively. This ensures that the module can function reliably in various challenging conditions.