Product image is representative; revision or series may vary. Contact us to request a specific version.
The RM7830A1029 from Honeywell is a relay control module suitable for on/off power burner applications. Its design supports a supply voltage of 120 VAC and operates within specified frequency limits.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Honeywell |
|---|---|
| Product Type | Relay Control Module |
| Product Line | 7800 Series |
| Part Number | RM7830A1029 |
| Burner Application Type | On/Off Power Burner |
| Pilot Flame Establishing Period | 3 seconds or 5 seconds |
| Main Flame Establishing Period | 3 seconds or 5 seconds |
| Supply Voltage | 120 VAC |
| Minimum Frequency | 50 Hz |
| Maximum Frequency | 60 Hz |
| Post-Purge Timing | 30 seconds |
| Early Spark Termination | Yes, 5 seconds |
| Minimum Ambient Temperature | -40°C |
| Maximum Ambient Temperature | 60 °C |
Model RM7830A1029 from the Honeywell 7800 Series is engineered as a relay control module for burner systems. Weighing in at 1.81 lbs, it is tailored for on/off power burner applications. This model operates on a supply voltage of 120 VAC while ensuring efficient performance within a frequency range of 50 Hz to 60 Hz.
The burner control specifics include a configurable pilot flame establishment period of either 3 or 5 seconds, which can be matched by the main flame establishment period. Additionally, it incorporates post-purge timing lasting for 30 seconds to ensure safe operation post-ignition.
An early spark termination feature enhances safety protocols as it allows for spark end after 5 seconds if the flame is not established. In terms of environmental resilience, this module is designed to operate effectively between minimum and maximum ambient temperatures of -40°C and 60°C, respectively. This ensures that the module can function reliably in various challenging conditions.