The Honeywell KS84230041 is an ionization pilot burner that operates efficiently within a capacity range of 1.2 to 2 kW. Designed for LPG gas, this burner features a compact size of 16 mm and is built with durable materials.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Honeywell |
|---|---|
| Product Type | Ionization Pilot Burner |
| Product Line | Other |
| Part Number | KS84230041 |
| Burner Size | 16 mm |
| Capacity | 1.2 to 2 kW |
| Gas Type | LPG |
| Gas Inlet Pressure | 20-45 mbar |
| Air Inlet Pressure | 30-70 mbar |
| Flame Length | Approx. 4 cm |
| Flame Control Type | Flame rod with single-electrode ionization |
| Ignition Type | Direct spark ignition (with 5kV ignition transformer) |
| Housing Material | Aluminum |
| Flame Tube Material | Heat-resistant steel |
| Max. Operating (Flame Tube Tip) Temperature | 1000 °C (900 °C for lambda <1) |
| Pipe Connection | Rp internal thread |
| Flame Tube Length | 400 mm |
The KS84230041 from Honeywell is an ionization pilot burner designed for reliable performance in various heating applications. With a burner size measuring 16 mm, it proves to be compact yet effective. This unit has a weight of 1.7 lbs, making it manageable for installation. The burner operates efficiently with a capacity ranging from 1.2 to 2 kW, making it well-suited for use with liquefied petroleum gas (LPG).
For appropriate operation, the gas inlet pressure should be set between 20 to 45 mbar, while the air inlet pressure must fall within 30 to 70 mbar. The burner creates a flame with an approximate length of 4 cm, which is stabilized through a flame rod utilizing a single-electrode ionization method. For ignition, it employs a direct spark ignition system powered by a 5kV ignition transformer, ensuring reliable starting each time.
The construction features an aluminum housing that enhances durability, while the flame tube is made from heat-resistant steel, capable of withstanding high temperatures. It can handle a maximum operating temperature at the flame tube tip of 1000 °C and can function at 900 °C for lambda values below 1. The connection for the gas piping utilizes an Rp internal thread, streamlining installation processes. Additionally, the flame tube measures 400 mm in length, providing suitable accommodation for efficient operation.