Product image is representative; revision or series may vary. Contact us to request a specific version.
The Honeywell SPXCDULNRFD operates as a fixed gas detector transmitter designed for remote detection of flammable gases. With a nominal voltage of 24 VDC, this unit effectively monitors environments under challenging conditions.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Honeywell |
|---|---|
| Product Type | Fixed Gas Detector Transmitter (Remote Flammable Detector) |
| Product Line | Sensepoint XCD |
| Part Number | SPXCDULNRFD |
| Voltage Rating | 16 to 32 VDC (24 VDC nominal) |
| IP Rating | IP66 |
| Operating Temperature Range | -40°C to +65°C |
| Storage Temperature Range | -25°C to +65°C |
| Humidity Range | Continuous 20-90% RH; Intermittent 0-99% RH (Non-Condensing) |
| Housing Color | Blue (epoxy painted aluminum) |
| Max. Power Consumption | 5 W |
| Current Output | Sink or source, 4-20mA (0-22mA range) |
| Relays | 3 x 5A at 250VAC, programmable NO/NC, energized/de-energized |
| Terminals | 18 x screw terminals, compatible with 20AWG to 14AWG wire |
| Cable/Conduit Entries | 3 x 3/4" NPT (UL/CSA version) |
| Enclosure Material | Epoxy painted LM25 aluminum alloy |
| Operating Pressure | 90-110 kPa |
The Honeywell SPXCDULNRFD is a specialized fixed gas detector transmitter, serving as a reliable solution for monitoring flammable gases. Weighing 4.4 lbs, this device is built with a durable epoxy painted aluminum housing in a distinctive blue color, ensuring visibility and corrosion resistance in various operational settings.
Designed to function within a voltage span of 16 to 32 VDC, with a nominal voltage at 24 VDC, the detector caters to specific power requirements and provides a maximum power consumption of 5 watts. The operating temperature range of this transmitter extends from -40°C to +65°C, making it suitable for extreme environments. Additionally, it supports storage temperatures varying from -25°C to +65°C.
For humidity management, the SPXCDULNRFD can operate continuously within 20-90% relative humidity and can handle intermittent humidity levels between 0-99% RH, all while avoiding condensation effects.
In terms of connectivity, it offers current output options that allow it to sink or source current in the range of 4-20 mA (with an extended range of 0-22 mA). The device is equipped with three relays that can handle 5A at 250VAC, and these relays are programmable for normally open (NO) or normally closed (NC) configurations, providing flexibility for system integration.
The transmitter’s terminal arrangement includes 18 screw terminals accommodating wire sizes from 20AWG to 14AWG, allowing for various wiring options. Also included are three conduit entries, each rated at 3/4” NPT for easy installation and integration into existing systems. The enclosure is constructed from LM25 aluminum alloy that has undergone epoxy painting, ensuring resistance to environmental factors.
Finally, it operates effectively under pressures from 90 to 110 kPa, reinforcing its functionality in dynamic gas detection applications.