The HE693THM449 model is a specialized input module designed by Horner Electric for thermocouple applications. With four channels, it allows for connection to various thermocouple types.

In Stock
Ships from Raleigh, NC
2 Year DO Supply Warranty
Not an Authorized Distributor: DO Supply is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All of our products come with DO Supply's 2-year warranty.
Learn more

Technical specifications for HE693THM449

ManufacturerHorner Electric
Product TypeThermocouple Input Module
Product LinePLC I/O
Part NumberHE693THM449
Weight0.56 lbs (0.26 kg)
Storage Temperature-40 to 85 °C
Humidity5% to 95% non-condensing
Channel-to-Bus Isolation1000VDC
Input Impedance>20MΩ
Maximum Safe Overload±35V
Number of Channels4
Thermocouple TypesJ, K, N, T, E, R, S
Temperature RangeJ: -210 to 760°C, K: -270 to 1372°C, N: -270 to 1300°C, T: -270 to 400°C, E: -270 to 1000°C, R: 0 to 1768°C, S: 0 to 1768°C
Resolution0.5°C
Accuracy±0.5°C typical (Type J)
Power Consumption70mA @ 5VDC, 60mA @ 24V Relay
Operating Temperature0 to 60 °C

The Horner Electric HE693THM449 is an input module tailored for thermocouple use, featuring four channels for flexible sensor connectivity. It accommodates a variety of thermocouple types, including J, K, N, T, E, R, and S, each catering to specific temperature ranges for accurate calculations.

With a resolution of 0.5°C and a typical accuracy of ±0.5°C, particularly for Type J thermocouples, the module ensures precise temperature readings. In terms of electrical characteristics, the HE693THM449 provides robust isolation of 1000VDC between channels and the bus, contributing to operational integrity in potentially hostile electrical environments.

The module can function within an operational temperature range of 0 to 60 °C. It also withstands storage conditions from -40 to 85 °C with a humidity tolerance of 5% to 95% without condensation. Input impedance exceeds 20MΩ, and the maximum safe overload is rated at ±35V, ensuring protection against input voltage variations. The power requirements include 70mA at 5VDC and 60mA at 24V relay, making it efficient for integration within control systems.