Johnson Controls' AS-VAV141-1 variable air volume (VAV) controller is utilized in HVAC systems. It has an N2 interface option, screw terminals, eight (8) analog inputs for temperature sensors and transmitters, four (4) binary inputs with dry contacts and a momentary push button, 0/2 analog outputs with 0 to 10 volts DC at 10 milliamps, and 8/6 binary outputs with 24 volts AC TRIAC options at 0.5 amps. It is powered by a 24V AC power supply.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Johnson Controls |
|---|---|
| Product Line | Metasys AS |
| Part Number | AS-VAV141-1 |
| Weight | 1.31 lbs (0.60 kg) |
| Series | Metasys FA |
| Type | Variable air volume (VAV) controller |
| Termination Type | Scew terminal |
| Number of Analog Inputs | 8 |
| Analog input options | RTD Temperature Element (NI, SI, or PT); 0-10 VDC Transmitter; 2K ohm Setpoint; Potentiometer |
| Number of Binary Inputs | 4 |
| Binary input options | 4-Dry Contacts; 1 Momentary Push Button from Zone Sensor |
| Number of Analog outputs | 0/2 |
| Analog output options | 0 to 10 VDC at 10 milliamps |
| Binary output options | 24 VAC Triacs at 0.5 amps |
| Power Requirements | 24 VAC at 50/60 Hz with 10 VA plus binary output load |
| Ambient Operating Temperature | 0 to 50°C (32 to 122°F) |
Johnson Controls produced the AS-VAV141-1, a variable air volume (VAV) controller originating from the Metasys FA sequences elements. It is intended to regulate VAV boxes, commonly used in heating, ventilation, and air conditioning (HVAC) applications to maintain optimum ventilation and temperature regulation in various zones. Without the enclosure, the controller's physical dimensions are 165mm in height, 163mm in width, and 51mm in depth. The enclosure adds 173mm to the height, 185mm to the width, and 119mm to the depth; together, diminutive proportions facilitate installation and integration within VAV cabinets and control panels. The AS-VAV141-1 controller is compatible with the N2 bus, which offers an isolated communication interface for communicating with other control system devices. The AS-VAV141-1's termination option is screw terminals, allowing for secure and convenient electrical connections. The controller provides eight analog inputs compatible with various sensors, including RTD temperature elements, 0 to 10VDC transmitters, two kilo-ohms setpoints, and potentiometers. This permits precise measurement and control of a variety of parameters. In addition, it has four binary inputs that can receive signals from dry contacts or a zone sensor's momentary press button. These inputs allow the controller to receive control and monitoring signals from the outside world. This AS-VAV141-1 outputs consist of 0/2 analog outputs that generate 0 to 10VDC signals at 10 milliamps. It also has 8/6 binary outputs with options for 24VAC rated TRIAC that can deliver up to 0.5 amps of current. These outputs permit the control of actuators and other VAV system components. This controller operates with an input frequency of 50/60 hertz and a voltage supply of 24V AC. It is specified to require 10 VA (volt-amp) in addition to the burdens of the binary outputs.