Product image is representative; revision or series may vary. Contact us to request a specific version.
The C500-OA223 TRIAC output unit from Omron combines compact design with reliability. With a weight of 0.6 kg and a C-shape form factor, this unit reinforces a practical solution for various applications.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Omron |
|---|---|
| Product Line | C500 |
| Part Number | C500-OA223 |
| Weight | 1.44 lbs (0.65 kg) |
| Description | TRIAC Output Unit |
| Max. Switching Capacity | 1 A, 250 VAC, 50/60 Hz (4 A/common, 5 A/Unit) |
| Min. Switching Capacity | 10 mA (resistive load), 40 mA (inductive load), 10 VAC |
| Leakage Current | 3 mA (100 VAC) max., 6 mA (200 VAC) max. |
| Residual Voltage | 1.2 V max |
| ON Response Time | 1 ms max |
| OFF Response Time | Half of load frequency max |
| Number of Points | 24 (8 points/common, 3 circuits) |
| Internal Current Consumption | 450 mA, 5 VDC max. |
| Fuse Capacity | 5 A, 250 V (two fuses) |
Omron's C500-OA223 is engineered as a TRIAC output unit, specifically designed to fulfill the needs of automation tasks. The dimensions of this unit exhibit a C-shape, making it suitable for various panel layouts. Weighing in at 0.6 kg, it provides portability without sacrificing performance.
This unit is capable of handling a maximum switching capacity of 1 A at 250 VAC, accommodating both 50 Hz and 60 Hz frequencies, with a broader rating of 4 A per common terminal and 5 A per unit. It also supports minimal switching capacities with a threshold as low as 10 mA for resistive loads and up to 40 mA for inductive applications, making it versatile in its usage.
Leakage current remains low, capped at 3 mA maximum for 100 VAC systems and 6 mA for 200 VAC arrangements. Furthermore, the residual voltage is maintained at a maximum of 1.2 V, ensuring efficient operation during active states. The device offers impressive response times; the ON response time is labeled as 1 ms or less, while the OFF response time is limited to a maximum of half the load frequency.
For functional capacity, it features a total of 24 points configured as 8 points per common with the arrangement of three circuits. The unit's internal current consumption is limited to 450 mA with a power supply of 5 VDC. To protect against overloads, it includes two fuses with a rating of 5 A at 250 V, ensuring durable operation under various conditions.