Product image is representative; revision or series may vary. Contact us to request a specific version.
The AS-B875-111 from Schneider Electric is an analog input module designed for precision measurement. It supports 8 differential channels and is versatile in voltage and current input ranges, accommodating various applications.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Schneider Electric |
|---|---|
| Product Type | Analog Input Module |
| Product Line | 800 Series |
| Part Number | AS-B875-111 |
| Weight | 2.00 lbs (0.91 kg) |
| Input Channels | 8 Differential inputs |
| Input Range (Voltage) | 1–5 VDC, 0–5 VDC, 0–10 V, ±5 V, ±10 V |
| Input Range (Current) | 4–20 mA, 0–20 mA, ±20 mA |
| Analog Filter | Single-pole low pass, -3 dB cutoff frequency at 48 Hz |
| Input Resistance (Voltage Mode) | >10 MΩ (in range), 10 kΩ (outside range) |
| Input Resistance (Current Mode) | 250 Ω ±0.05% |
| Input Protection | 120 V RMS (Normal and Common Mode) |
| Throughput Time | 10 ms for 8 channels, 20 ms for 16 channels |
| Accuracy | 0.1% absolute accuracy over temperature range |
| Conversion Resolution | >12 bits |
| Linearity Error | 0.05% of full scale |
| Isolation | 1500 VAC RMS for 1 minute (Input to OURBUS and Case) |
| Power Requirements | 5V at 500mA, 4.3V at 900 mA |
| Terminal Connector | AS-8535-000 |
The Schneider Electric AS-B875-111 is an analog input module suited for processing differential signals. This product can handle 8 input channels with a significant voltage range from 1–5 VDC to ±10 V. It also supports current inputs between 4–20 mA, 0–20 mA, and ±20 mA, making it flexible across measurement tasks.
Input resistance in voltage mode exceeds 10 MΩ within the specified range, ensuring minimal loading effects, while it registers at 10 kΩ outside the designated range. For current mode, the input resistance is maintained at 250 Ω ±0.05%, providing stable measurements.
The module incorporates a single-pole low pass filter rated with a -3 dB cutoff frequency at 48 Hz. Additionally, this unit provides input protection handling up to 120 V RMS for normal and common mode, safeguarding against unexpected voltage spikes.
With a throughput time of 10 ms for 8 channels and 20 ms for 16 channels, the AS-B875-111 ensures efficient signal processing. Its linearity error is maintained at just 0.05% of full scale, while conversion resolution exceeds 12 bits, delivering precise conversions.
For electrical isolation, it withstands 1500 VAC RMS for one minute between the inputs and the OURBUS as well as the enclosure, ensuring safe operation in potentially hazardous environments. Power requirements include 5V at 500 mA and 4.3V at 900 mA, supporting energy-efficient functionality. The terminal connector required for this module is the AS-8535-000.