The HLA36100 circuit breaker belonging to Schneider Electric's PowerPact series is designed to handle a rated operating voltage of up to 690 Volts AC. This device features three poles and a line rated current of 100 Amperes. With its toggle control mechanism, it allows precise management of electrical flow.

In Stock
Ships from Raleigh, NC
2 Year DO Supply Warranty
Not an Authorized Distributor: DO Supply is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All of our products come with DO Supply's 2-year warranty.
Learn more

Technical specifications for HLA36100

ManufacturerSchneider Electric
Product TypeCircuit breaker
Product LinePowerPact
Part NumberHLA36100
UPC785901700630
Weight5.38 lbs (2.44 kg)
Breaking Capacity CodeL
Rated Operating Voltage690 Volts AC
Number of Poles3 poles
Mounting Height4.3 inches (114.3 millimeters)
Line Rated Current100 Amperes
Control TypeToggle control
Breaking Capacity20 kiloamperes at 250 Volts DC, 50 kiloamperes at 500 Volts DC, 125 kiloamperes at 240 Volts AC, 100 kiloamperes at 480 Volts AC, and 50 kiloamperes at 600 Volts AC
Trip Unit TechnologyThermal-magnetic
Magnetic Tripping Current1,700 Amperes
Mounting MethodI-Line bracket
Ambient Operating Temperature-25 to 70°C (in a non-condensing environment)
Storage Temperature-50 to 85°C (in a non-condensing environment)
Magnetic Hold Current900 Amperes
Electrical Connection TypeI-Line connection, lugs line, and lugs load

The Schneider Electric HLA36100 is a highly capable circuit breaker part of the PowerPact series, tailored for extensive use in various electrical systems. With a maximum rated operating voltage of 690 volts AC and a line rated current of 100 amperes, the structure supports robust performance across two key voltage ratings. The device is equipped with three poles for effective multi-phase applications.

A toggle control provides straightforward manual operation, ensuring users can manage electrical flow easily. The breaker showcases a breaking capacity dependent on the specified voltage: 20 kiloamperes at 250 Volts DC, 50 kiloamperes at 500 Volts DC, and high capacities of 125 kiloamperes at 240 Volts AC, 100 kiloamperes at 480 Volts AC, and 50 kiloamperes at 600 Volts AC. The dependable thermal-magnetic trip unit technology includes a magnetic tripping current of 1,700 amperes. The magnetic hold current is 900 amperes, which maintains the breaker under specific operational conditions without tripping.

For installation, the unit utilizes an I-Line bracket, positioned at a mounting height of 4.3 inches (114.3 millimeters). Regarding temperature tolerances, the ambient operating range spans from -25 to 70°C in non-condensing conditions. For storage, it can endure temperatures from -50 to 85°C, maintaining reliability in varying conditions. The HLA36100 presents I-Line connections for electrical integration with external systems, utilizing line and load lugs for secure connections, ensuring long-term effectiveness and safety in power distribution.