Product image is representative; revision or series may vary. Contact us to request a specific version.
The HJA36015 is a molded-case circuit breaker produced by Schneider Electric within the Square D series. This unit features a continuous current rating of 15 amps and is rated for both 480 V AC and 250 V DC, making it suitable for various applications.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Schneider Electric |
|---|---|
| Product Type | Molded-case circuit breaker |
| Product Line | Square D |
| Part Number | HJA36015 |
| Weight | 4.88 lbs (2.21 kg) |
| Tightening Torque | 5 N·m (AWG 14-3/0) |
| Continuous Current Rating | 80% |
| Current Rating | 15 A |
| Voltage Rating | 480 V AC/250 V DC |
| Number of Poles | 3 Poles |
| Breaking Capacity | 100 kA at 120/240 VAC; 65 kA at 277/480 VAC; 10 kA at 250 VDC |
| Trip Unit Technology | Thermal-magnetic |
| Mounting Mode | I-Line |
| Electrical Connection | I-Line (line)/Lugs (load) |
| Wire Gauge | AWG 14-4 (Cu) or AWG 12-4 (Al) |
| Phase Connection | ABC |
| Magnetic Hold Current | 350 A |
| Magnetic Tripping Current | 750 A |
| Breaking Capacity Code | J code |
In the realm of electrical distribution, the HJA36015 circuit breaker by Schneider Electric stands out as a molded-case circuit breaker tailored for efficient performance. With a current rating of 15 A, it is designed to operate within a voltage range of 480 V AC and 250 V DC. This unit operates with an impressive continuous current rating set at 80%.
Structured with three poles, it delivers reliable circuit protection while being equipped with thermal-magnetic trip technology for dependable operation under intermittent fault conditions. The capacity to break a fault at high levels is noteworthy, as it can handle a breaking capacity of 100 kA at 120/240 VAC, 65 kA at 277/480 VAC, and 10 kA at 250 VDC.
Mounting is facilitated via the I-Line setup, allowing for a straightforward installation process. The electrical connections feature I-Line for line input and lugs for load output, which accommodate efficient wire management. This breaker supports wire gauges of AWG 14 to AWG 4 when using copper conductors, as well as AWG 12 to AWG 4 for aluminum cables.
Additional specifications include a magnetic hold current rating of 350 A, with a magnetic tripping current threshold set at 750 A, reflecting the robustness of this device. The tightening torque requirement stands at 5 N·m, compatible with AWG 14-3/0 sized wires. Finally, this circuit breaker is designated with a J code for its breaking capacity, indicative of its capability in demanding environments.