Product image is representative; revision or series may vary. Contact us to request a specific version.
The 6SL3120-2TE21-0AA3 from Siemens is a dual-motor drive module within the SINAMICS series. Its voltage output range allows for up to 0.717 of the DC-link voltage, allowing it to efficiently handle power requirements.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Siemens |
|---|---|
| Product Line | SINAMICS |
| Part Number | 6SL3120-2TE21-0AA3 |
| UPC | 662643432978 |
| Weight | 15.00 lbs (6.80 kg) |
| Product Classification | Dual motor drive module |
| Voltage Output Range | 0 to 0.717 of the DC-link voltage |
| Nominal Current per Channel | 2 × 9 amps |
| Continuous Operating Current | 2 × 7.7 amps |
| Short-term Overload Current (40%) | 2 × 10 amps |
| Maximum Instantaneous Current | 2 × 18 amps |
| Device Mass | 5.5 kilograms |
| Cooling System Design | Built-in air circulation fan |
| Highest Operational Temperature | 40°C normal, 55°C with reduced capacity |
| Energy Loss During Operation | 187.6 watts |
| Auxiliary Power Supply Voltage | 24 volts DC (20.4 to 28.8 volts range) |
| Auxiliary Power Supply Current Draw | 1.15 amps DC |
| DC Power Bus Voltage Range | 510 to 720 volts DC |
| Maximum DC-Link Current Capacity | 22 amps DC |
| Capacitance of the DC-Link Circuit | 220 μF |
Siemens' 6SL3120-2TE21-0AA3 is a dual-motor drive module designed to efficiently operate various applications. This unit features a voltage output range reaching up to 0.717 of the DC-link voltage. It is rated for a nominal current of 9 amps on each channel, while the continuous operating current is rated at 7.7 amps for sustained usage.
It can handle short currents of up to 10 amps for brief overload conditions at a 40% duty cycle. The highest instantaneous current can spike to 18 amps, ensuring robust performance when needed. The unit's considerable weight of 5.5 kilograms contributes to its stability during operations. An integrated cooling mechanism utilizing an air circulation fan aids in maintaining optimal temperatures while running.
The module operates effectively in environments with a maximum temperature of 40°C but can handle up to 55°C when capacity is somewhat reduced. During operation, it dissipates energy losses of 187.6 watts. It functions with an auxiliary power supply voltage of 24 volts DC, ranging from 20.4 to 28.8 volts, and draws a current of 1.15 amps DC from this supply.
The DC power bus voltage span acceptable for the module ranges from 510 volts to 720 volts DC. Additionally, it can accommodate a maximum DC-link current capacity of 22 amps DC. The capacitance of the DC-link circuit is rated at 220 μF, which supports stable operation under varying conditions.