2711P-T9W22D8S-B
With an aspect ratio of 5:3, this operator terminal maintains a display resolution of 800 x 480 pixels. It supports various network topologies including linear, star, and Device-Level Ring (DLR). The
The Allen Bradley Panelview Plus 7 is an Operator Interface Terminal which has a display size ranging from 4 inches to 10 inches. They use WIndows CE 6.0 and can be programmed with Factory Talk View Machine Edition. These terminals are capable of monitoring an application remotely using a VNC connection. This module includes 512 MB of Ram and uses an SD card to copy and restore the operator interface.
Browse available units in our catalog of Panelview Plus 7.
With an aspect ratio of 5:3, this operator terminal maintains a display resolution of 800 x 480 pixels. It supports various network topologies including linear, star, and Device-Level Ring (DLR). The
This operator interface boasts two 10/100Base-T Ethernet ports for communication needs. Its TFT color display provides a resolution of 480 x 272 pixels with a typical brightness of 300 nits. The viewi
This model incorporates two 10/100Base-T Ethernet ports, allowing seamless connectivity within network structures like linear, star, and Device-Level Ring (DLR). The touch input facilitates intuitive
This operator interface terminal operates with an input voltage range from 100 to 240 volts AC, allowing versatility in power supply connections. The touchscreen supports a maximum of one million actu
This PanelView model is designed to function within a safe voltage input of 18 to 30 V DC, utilizing a dual-core ARM Cortex-A9 processor. The device offers 1 GB of memory and includes 512 MB of non-vo
This operator interface includes a conformal coat for enhanced durability and protection. It utilizes a 24 VDC input voltage and provides 512 MB of RAM and storage, allowing for efficient data managem
This adapter plate kit includes a touch keypad and has overall dimensions of 20.16 inches in length and 13.43 inches in width. The design supports operating humidity levels between 5% and 95% without
This operator interface is designed for panel mounting and is oriented in landscape mode. It operates at a control voltage of 24 VDC and includes an embedded switch for connectivity, supporting Device
This interface terminal uses a 24V DC input for operation and has a power rating of 50 W. The display measures 10.4 inches diagonally and boasts an 800 x 600 VGA resolution. The device includes two US
This logic module includes 512 MB of RAM and non-volatile memory. The 8-wire analog resistive touchscreen interface allows for intuitive operation, complemented by a stainless-steel membrane keypad wi
Two status indicators are located on the back of your PanelView Plus 7 terminal. The STS indicator is green and communicates that the terminal is powered on and operating. The ERR indicator is red and communicates hardware and or firmware faults. Upon starting your terminal, both indicators will initially flash, and the STS indicator will continue to flash as startup progresses. If the indicators do not turn on, always check the power cable. Once the startup has completed successfully, the STS indicator remains on. See the table below if the terminal stops during the startup process:
| ERR Indicator (Red) | STS Indicator (Green) | Meaning/Action |
| Possibly Recoverable Error | ||
| Blinking | Off | Firmware error. Redownload firmware. |
| Failed configuration. Restore factory default image. | ||
| Fatal Error | ||
| On | Blinking | Display hardware error. Replace the terminal. |
| On | Hardware error. Replace the terminal. | |
If your PanelView Plus 7 terminal fails to startup, always check for adequate power first. Verify the terminal's DC power requirements are being met. Startup failures can also be caused by incorrect wiring. Review the wire specifications for your terminal and verify that the DC power wiring is correct. Check the status indicators. See the table above. Ensure noting is touching the display during startup, as this may cause startup errors. Finally, ensure the progress indicator has not stalled. If it has stalled, reload the firmware or restore the terminal to factory default settings.
If your PanelView Plus 7 terminal is restarting for seemingly no reason, first check for incorrect wiring. Review the wire specifications for your terminal and verify the DC power wiring is correct. Intermittent terminal restarts can also be caused by the processor overheating. Check the processor temperature, the operating temperature, and review the System Event log for over-temperature conditions. Also, verify that there is adequate clearance around the terminal.
| Issue | Action |
| Temperatures Beyond Operating Range | Check the Monitors tab to review temperatures. Normal operation will not resume until the system has cooled to a normal operating temperature. |
| Low Display Brightness |
Adjust the Brightness Setting - Select Terminal Settings> Display> Display Intensity Use the arrows to change the intensity and press Enter to save |
| Low Screen Saver Brightness |
Adjust the Screen Saver Setting - Select Terminal Settings> Display> Screen Saver Use the arrows to adjust the intensity and press Enter to save |
| Issue | Action |
| Touchscreen Nonfunctional | Verify the touchscreen is not damaged. If it is, the terminal must be replaced |
| Incorrect Calibration | Recalibrate the touchscreen |
| Touching Multiple Input Points | The touchscreen does not support multiple operations simultaneously. Ensure you do not touch multiple input elements at once and that you do not rest your hand on the display. |
| Issue | Action |
| Cable Connections are Poor | Verify network connections and check the status indicators. The green indicator will turn on when a link has been established and the yellow indicator will blink when activity is detected. |
| Invalid Ethernet Connection | Ensure there is a good connection to the hub and uplink ports. Poor cable quality and crimping can inhibit the ethernet connection. |
|
Invalid IP Address |
Check the DHCP. If this is enabled the device will attempt to connect to a valid IP address within seconds of startup. If it fails to acquire and IP address, the TCP/IP protocol will assign 169.254.xxx.xxx. |
| Conflicting IP Addresses | Check the DHCP. If the DHCP is not enabled, verify the IP address specified does not conflict with another device on the network. |
Here at DO Supply, we offer repair services for your Allen-Bradley products, such as the Allen-Bradley PanelView Plus 7. Click here for more information or to request a quote