2711P-B7C22D9P-B
This model operates on a 24 VDC input voltage, with a range of 18 to 30 VDC during operation. The display's brightness reaches 300 cd/m², and it has an aspect ratio of 4:3. It provides a viewing area
The Allen Bradley Panelview Plus 7 is an Operator Interface Terminal which has a display size ranging from 4 inches to 10 inches. They use WIndows CE 6.0 and can be programmed with Factory Talk View Machine Edition. These terminals are capable of monitoring an application remotely using a VNC connection. This module includes 512 MB of Ram and uses an SD card to copy and restore the operator interface.
Browse available units in our catalog of Panelview Plus 7.
This model operates on a 24 VDC input voltage, with a range of 18 to 30 VDC during operation. The display's brightness reaches 300 cd/m², and it has an aspect ratio of 4:3. It provides a viewing area
This Panelview Plus 7 terminal includes ample memory with 4 GB RAM and 19.87 GB of storage, in addition to 2 GB of nonvolatile storage dedicated to applications. It supports a wide range of operationa
This panel interface includes a touch screen using analog resistive technology for user input. It operates at a nominal input voltage of 24 Volts DC, and features dual Ethernet ports for network commu
This operator interface is constructed with a 15-inch display featuring a 4:3 aspect ratio. It comes equipped with 512 megabytes of storage memory and another 512 megabytes of RAM. The device operates
This operator terminal is built with 4 GB of RAM and provides 19.87 GB of storage alongside 2 GB of nonvolatile storage dedicated to applications. The display resolution reaches 1024 x 768 XGA with vi
The Allen Bradley 2711P-T9W22A9P Panelview Plus 7 Terminal is a Performance Model with a Touchscreen, a 9 WVGA Wide aspect ratio Color Display, and with One Ethernet Port. It is 100-240VAC Powered.
Designed for robust industrial applications, this terminal features a viewing area of 115 x 68 mm (4.5 x 2.6 inches) and includes two 10/100Base-T Ethernet ports for network connectivity. The operator
This performance graphic terminal includes a touch input with a keypad, supporting an actuation rating of one million presses. It incorporates two USB Type A high-speed host ports and one Type B devic
This operator interface terminal is equipped with an analog resistive touchscreen, facilitating user interaction. The display luminance reaches approximately 300 cd/m², enhancing visibility. It featur
This operator interface terminal features a typical screen brightness of 300 nits and utilizes a tough TFT color liquid crystal display for vibrant visuals. It supports touch input with a substantial
Two status indicators are located on the back of your PanelView Plus 7 terminal. The STS indicator is green and communicates that the terminal is powered on and operating. The ERR indicator is red and communicates hardware and or firmware faults. Upon starting your terminal, both indicators will initially flash, and the STS indicator will continue to flash as startup progresses. If the indicators do not turn on, always check the power cable. Once the startup has completed successfully, the STS indicator remains on. See the table below if the terminal stops during the startup process:
| ERR Indicator (Red) | STS Indicator (Green) | Meaning/Action |
| Possibly Recoverable Error | ||
| Blinking | Off | Firmware error. Redownload firmware. |
| Failed configuration. Restore factory default image. | ||
| Fatal Error | ||
| On | Blinking | Display hardware error. Replace the terminal. |
| On | Hardware error. Replace the terminal. | |
If your PanelView Plus 7 terminal fails to startup, always check for adequate power first. Verify the terminal's DC power requirements are being met. Startup failures can also be caused by incorrect wiring. Review the wire specifications for your terminal and verify that the DC power wiring is correct. Check the status indicators. See the table above. Ensure noting is touching the display during startup, as this may cause startup errors. Finally, ensure the progress indicator has not stalled. If it has stalled, reload the firmware or restore the terminal to factory default settings.
If your PanelView Plus 7 terminal is restarting for seemingly no reason, first check for incorrect wiring. Review the wire specifications for your terminal and verify the DC power wiring is correct. Intermittent terminal restarts can also be caused by the processor overheating. Check the processor temperature, the operating temperature, and review the System Event log for over-temperature conditions. Also, verify that there is adequate clearance around the terminal.
| Issue | Action |
| Temperatures Beyond Operating Range | Check the Monitors tab to review temperatures. Normal operation will not resume until the system has cooled to a normal operating temperature. |
| Low Display Brightness |
Adjust the Brightness Setting - Select Terminal Settings> Display> Display Intensity Use the arrows to change the intensity and press Enter to save |
| Low Screen Saver Brightness |
Adjust the Screen Saver Setting - Select Terminal Settings> Display> Screen Saver Use the arrows to adjust the intensity and press Enter to save |
| Issue | Action |
| Touchscreen Nonfunctional | Verify the touchscreen is not damaged. If it is, the terminal must be replaced |
| Incorrect Calibration | Recalibrate the touchscreen |
| Touching Multiple Input Points | The touchscreen does not support multiple operations simultaneously. Ensure you do not touch multiple input elements at once and that you do not rest your hand on the display. |
| Issue | Action |
| Cable Connections are Poor | Verify network connections and check the status indicators. The green indicator will turn on when a link has been established and the yellow indicator will blink when activity is detected. |
| Invalid Ethernet Connection | Ensure there is a good connection to the hub and uplink ports. Poor cable quality and crimping can inhibit the ethernet connection. |
|
Invalid IP Address |
Check the DHCP. If this is enabled the device will attempt to connect to a valid IP address within seconds of startup. If it fails to acquire and IP address, the TCP/IP protocol will assign 169.254.xxx.xxx. |
| Conflicting IP Addresses | Check the DHCP. If the DHCP is not enabled, verify the IP address specified does not conflict with another device on the network. |
Here at DO Supply, we offer repair services for your Allen-Bradley products, such as the Allen-Bradley PanelView Plus 7. Click here for more information or to request a quote