The IC200PNS001 is an Profinet network interface unit that is part of the VersaMax series, formerly manufactured by GE Intelligent Platforms (GE IP), now under Emerson Automation. This module is mainly used to implement distributed I/O architecture as it supports communication up to 2880 total bytes of discrete I/O data and 2880 bytes of analog I/O data over Profinet network at communication speed of 10/100 mbps at maximum distance of 100 meters per segment. This module specifically supports Profinet Slave version 2.2 Class A I/O. This module comes with Two (2) RJ45 connectors and supports linear, daisy-chain and star topologies.

In Stock
Ships from Raleigh, NC
2 Year DO Supply Warranty
Not an Authorized Distributor: DO Supply is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All of our products come with DO Supply's 2-year warranty.
Learn more

Technical specifications for IC200PNS001

ManufacturerGE Fanuc Emerson
Product typeRemote I/O Profinet Network Interface Unit
Product LineVersamax
Part NumberIC200PNS001
Weight0.75 lbs (0.34 kg)
Power Consumption0.60 Amperes at 5 Volts DC
Product DescriptionProfinet network interface unit
Supported protocolPROFINET version Version 2.2 Class A IO-Device
Supported ProtocolsPROFINET Slave, Version 2.2 Class A IO-Device
Proficy Machine Edition Version RequiredVersion 7.0 or later
Supported topologiesLinear, Star, Ring (redundant)
No. of PortsTwo (2) RJ45ports
Module DimensionsHeight: 132mm (5.2 inches), Width: 134mm (5.28 inches)
Distance100 m
Number of Port ConnectorsTwo RJ-45
Transmission rate10/100 mbps
Transmission speed10/100 mbps
I/O Discrete Points2880 bytes total 1440 bytes of input data 1440 bytes of output data
Maximum cable distance100 meters per segment
PNS Status and Control Bits32 input status bits and 32 output control bits
I/O Analog Words2880 bytes total 1440 bytes of input data 1440 bytes of output data
MountingDIN Rail
I/O Data Update on the PROFINET LANConfigurable: 1ms, 2ms, 4ms, 8ms, 16ms, 32ms, 64ms, 128ms, 256ms and 512ms
No. of modulesEight (8) modules
No. of supported I/O modulesup to Eight (8) modules
RoHS ComplianceYes
No. of racksNot supported
Operating Temperature Range0 to 60 degrees Celsius surrounding air temperature without a fan
I/O Update rateConfigurable: 1ms, 2ms, 4ms, 8ms, 16ms, 32ms, 64ms, 128ms, 256ms and 512ms
Compatible controllersSeries 90-70; PACSystem RX7i; PACSystem RX3i
Diagnostic data32 input status bits; 32 output control bits
I/O Data update rate1ms, 2ms, 4ms, 8ms, 16ms, 32ms, 64ms, 128ms, 256ms and 512ms

The IC200PNS001 is a Profinet network interface unit from the VersaMax product family. It is mainly used to implement distributed I/O architecture utilizing Profinet industrial protocol specifically, Profinet slave Version 2.2 Class A I/O Device. This module can be used not only with VersaMax series but with other controllers such as PACSystem RX3i and RX7i controllers. The IC200PNS001 is installed with Two (2) RJ45 ports that functions as an embedded switch and utilizes a single IP address only. can be used in different Ethernet topologies specifically, linear, star and ring. Both port supports 10/100 mbps transmission rate and able to handle a total of 2880 bytes of discrete input and output specifically, 1440 bytes of input data and 1440 bytes of output data. Similarly, this module can process up to 2880 bytes of analog I/O particularly, 1440 bytes of analog input and 1440 bytes of analog output. For diagnostic data, this module has built-in 32 input status bits and 32 output control bits. Up to Eight (8) VersaMax I/O modules and carriers can be installed per instance of IC200PNS001. It has configurable data update rates of 1ms, 2ms, 4ms, 8ms, 16ms, 32ms, 64ms, 128ms, 256ms and 512ms. This module has 5 VDC backplane current consumption of 3 Watts and physically measures 134mm (5.28 in) x 132mm (5.2 in). The IC200PNS001 uses 10/100BASE-T transmission media with maximum cable distance of 100 meters per segment which can be extended with the use of ethernet switches or media converters such as fiber optic media converter.

The GE Fanuc Versamax IC200PNS001 PROFINET Scanner (PNS) module requires an RX3i PLC CPU with Firmware version 7.0 or newer and the Proficy Machine Edition software version 7.0 or later. The module coordinates the Versamax remote node with the PROFINET I/O network. The GE Fanuc IC200PNS001 PROFINET Scanner (PNS) module has functions such as input data retrieval and output data delivery. It has features such as PROFINET alarms and diagnostics reporting, which allows for the hot swap of an excessive power supply that has been de-energized and it allows for configuration with the Classless InterDomain Routing with supernetting and subnetting. It also offers field upgrade options, and the firmware can be updated via the USB port (the port is intended for firmware upgrades only and not for a permanent connection). The GE Fanuc IC200PNS001 PROFINET Scanner (PNS) module can connect the remote node to the PROFINET I/O network to oversee the I/O status if the communication is lost. Other functions include module scanning (both output and input scans), managing the module configuration, PROFINET communication between modules and I/O controllers within the PROFINET Scanner node, and reporting or issuing fault information in the form of diagnostics and alarms to the I/O controller. In addition, the PNS module’s main remote I/O publishes data on the PROFINET network to an I/O controller and it receives the data generated from an I/O controller on the PROFINET network. This module has an operating temperature range between 0 and 60 degrees Celsius for the surrounding air temperature with no fan.

Revision Part #Also known as
IC200PNS001AAIC200PNS001-AA, Series AA, Rev AA
IC200PNS001ABIC200PNS001-AB, Series AB, Rev AB
IC200PNS001ACIC200PNS001-AC, Series AC, Rev AC
IC200PNS001CCIC200PNS001-CC, Series CC, Rev CC