| Manufacturer | Omron |
|---|---|
| Product Line | C500 |
| Part Number | C500-OA222 |
| Weight | 1.00 lbs (0.45 kg) |
| Description of Module | TRIAC Output Unit |
| Max. Switching Capacity | 1 A, 132 VAC, 50/60 Hz (4 A/common, 5 A/Unit) |
| Min. Switching Capacity | 10 mA (resistive load), 40 mA (inductive load), 10 VAC |
| Leakage Current | 3 mA (100 VAC) max., 6 mA (200 VAC) max. |
| Residual Voltage | 1.2 V max. |
| ON Response Time | 1 ms max. |
| OFF Response Time | 1/2 of load frequency max. |
| Number of Points | 16 (8 points/common, 2 circuits) |
| Internal Current Consumption | 300 mA, 5 VDC max. |
| Fuse Capacity | 5 A, 250 V (two fuses) |
Omron's C500-OA222 is categorized as a TRIAC output module designed for versatility and efficiency. Weighing only 0.5 kg, this unit integrates into various control systems without adding significant bulk. This output module is capable of a maximum switching capacity of 1 A, supporting voltages up to 132 VAC with operational frequencies of 50 to 60 Hz. Notably, it allows a higher capacity for common points, up to 4 A. For individual unit functions, it handles a maximum of 5 A.
The minimum switching capacity indicates that the device can operate loads as low as 10 mA for resistive loads and 40 mA for inductive loads, while it maintains functionality at voltages as low as 10 VAC. Leakage currents peak at 3 mA for 100 VAC and 6 mA for 200 VAC, ensuring reliable operation without excess loss.
Residual voltage is capped at 1.2 V maximum, contributing to efficient state changes within the system. When activated, the module demonstrates an ON response time of up to 1 ms. The OFF response time is determined by load frequency, creating efficient disengagement under operational conditions.
The unit features two circuits of 8 output points each, summing to a total of 16 points for robust application support. Its internal current consumption is rated at a maximum of 300 mA at 5 VDC. Designed with safety in mind, the module includes two fuses rated at 5 A and 250 V. Dimensions conform to the A-shape standard, allowing for easy integration into corresponding panel setups.