Product image is representative; revision or series may vary. Contact us to request a specific version.
The AS-B804-116 from Schneider Electric is an output module designed to handle a rated output voltage of 115 VAC. This module is configured to support a total of 16 points, organized into two distinct groups, with each group managing up to 8 outputs.
We sell industrial automation parts backed by our free 2-Year DO Supply Warranty.
Same-day domestic and fast international shipping with UPS, FedEx, DHL, and more.
AMEX, Visa, MasterCard, Discover, wire transfer, net terms, and more.
Repairs and exchanges are available for all automation products.
Drop shipping, blind shipping, and account shipping with no extra fees.
| Manufacturer | Schneider Electric |
|---|---|
| Product Line | Modicon |
| Part Number | AS-B804-116 |
| UPC | 782451041954 |
| Weight | 2.69 lbs (1.22 kg) |
| Name of Module | Output Module |
| Output Voltage Rating | 115 VAC Output |
| Number of Points | 16 |
| Operating Voltage | 80 to 130 VAC continuous / 47 to 63 Hz |
| Number of Groups | 2 |
| Output per Group | 8 |
| ON Current Maximum per Point | 2 A continuous |
| ON Current Surge | 50 A (1 cycle) |
| Maximum ON Current per Group | 6 A |
| Maximum Load ON Current | 25 mA |
| Maximum OFF Leakage Current | 3 mA @ 115 VAC |
| Voltage Drop | 1.5 V @ 2 A |
| Maximum Response Time | 8.3 ms @ 60 Hz |
| Power Required | 76 mA (+5V), 480 mA (+4.3V), and 0 mA (-5V) |
| Operating Temperature | 0 to 60°C |
The Schneider Electric Modicon AS-B804-116 model is categorized as an output module. This device can manage a voltage rating of 115 VAC and features 16 points, which are divided into two groups with 8 outputs each. Operating within a voltage range of 80 to 130 VAC continuously, this module operates effectively across a frequency range of 47 to 63 Hz. Each output point can continuously handle an ON current of 2 A, supporting momentary surge currents of up to 50 A for a single cycle. Additionally, the maximum ON current allowed per group is 6 A, facilitating reliable function in demanding applications.
The module also imposes a maximum load ON current of 25 mA, ensuring compatibility with various connected loads. In terms of leakage, the maximum OFF leakage current is kept to 3 mA at 115 VAC, maintaining safety and performance standards. In operational context, the voltage drop across the module is measured at 1.5 V with an output current of 2 A, indicating energy efficiency during operation. Response capability is noteworthy, with a maximum response time of 8.3 ms at 60 Hz, allowing for swift action in control processes. Power consumption is specified at 76 mA for +5V, 480 mA for +4.3V, and 0 mA for -5V supply voltages. Finally, the device is built to function within a temperature range of 0 to 60°C, accommodating a variety of environmental conditions.