The AS-B804-116 from Schneider Electric is an output module designed to handle a rated output voltage of 115 VAC. This module is configured to support a total of 16 points, organized into two distinct groups, with each group managing up to 8 outputs.

In Stock
Ships from Raleigh, NC
2 Year DO Supply Warranty
Not an Authorized Distributor: DO Supply is not an authorized distributor for listed manufacturers or tradenames and therefore the manufacturer's warranty does not apply. All of our products come with DO Supply's 2-year warranty.
Learn more

Technical specifications for AS-B804-116

ManufacturerSchneider Electric
Product LineModicon
Part NumberAS-B804-116
UPC782451041954
Weight2.69 lbs (1.22 kg)
Name of ModuleOutput Module
Output Voltage Rating115 VAC Output
Number of Points16
Operating Voltage80 to 130 VAC continuous / 47 to 63 Hz
Number of Groups2
Output per Group8
ON Current Maximum per Point2 A continuous
ON Current Surge50 A (1 cycle)
Maximum ON Current per Group6 A
Maximum Load ON Current25 mA
Maximum OFF Leakage Current3 mA @ 115 VAC
Voltage Drop1.5 V @ 2 A
Maximum Response Time8.3 ms @ 60 Hz
Power Required76 mA (+5V), 480 mA (+4.3V), and 0 mA (-5V)
Operating Temperature0 to 60°C

The Schneider Electric Modicon AS-B804-116 model is categorized as an output module. This device can manage a voltage rating of 115 VAC and features 16 points, which are divided into two groups with 8 outputs each. Operating within a voltage range of 80 to 130 VAC continuously, this module operates effectively across a frequency range of 47 to 63 Hz. Each output point can continuously handle an ON current of 2 A, supporting momentary surge currents of up to 50 A for a single cycle. Additionally, the maximum ON current allowed per group is 6 A, facilitating reliable function in demanding applications.

The module also imposes a maximum load ON current of 25 mA, ensuring compatibility with various connected loads. In terms of leakage, the maximum OFF leakage current is kept to 3 mA at 115 VAC, maintaining safety and performance standards. In operational context, the voltage drop across the module is measured at 1.5 V with an output current of 2 A, indicating energy efficiency during operation. Response capability is noteworthy, with a maximum response time of 8.3 ms at 60 Hz, allowing for swift action in control processes. Power consumption is specified at 76 mA for +5V, 480 mA for +4.3V, and 0 mA for -5V supply voltages. Finally, the device is built to function within a temperature range of 0 to 60°C, accommodating a variety of environmental conditions.