140G-G3C4-C90
This unit features four poles and incorporates fixed thermal and magnetic protection systems. The 140G-G3C4-C90 has a current range of 90 A, with a thermal trip setting at 90 A and a magnetic trip val
The Allen Bradley 140G molded case circuit breakers are suitable for a wide range of applications in low-voltage 3-phase power systems. 140G series circuit breakers can be reverse-fed. They provide overcurrent protection to conductors and other equipment, and they can be used as the main disconnecting devices for control panels. The 140G circuit breakers can also be used for branch circuit protection or as feeder breakers.
Browse available units in our catalog of 140G MCB.
This unit features four poles and incorporates fixed thermal and magnetic protection systems. The 140G-G3C4-C90 has a current range of 90 A, with a thermal trip setting at 90 A and a magnetic trip val
This molded case circuit breaker is built upon an H frame and features fixed thermal and magnetic protection types. The current range it supports is set at 60 A while maintaining a rated insulation vo
This molded case circuit breaker is designed with an H frame and operates across a current range starting at 50 A. Its protection mechanisms include fixed thermal and fixed magnetic options. It mainta
Incorporating fixed thermal and magnetic protection types, this model operates effectively within a current range of up to 35 A. It features a rated insulation voltage of 1000 V and an impulse withsta
This molded case circuit breaker features adjustable thermal and magnetic protection types. The effective current range is rated at 100 Amps. It can withstand a rated insulation voltage of 1000 V and
Designed for high-performance applications, the 140G-H15H4-C60 circuit breaker operates at a maximum current of 125 Amps. It employs Electronic LSI for its protection type and includes four poles. Thi
This circuit breaker has a trip unit rating that accommodates various applications. It is constructed with an HC frame and provides an insulation voltage rating of 1000 volts. With an impulse withstan
This model features a frame type I and supports fixed thermal and magnetic protection. It can manage a current range up to 120 A, with a thermal trip set at 120 A and a magnetic trip capable of 1200 A
The 140G-JTI3-D15 belongs to the J frame product line and has a rated current of 150 Amps. This circuit breaker is rated for an insulation voltage of 1000 volts and can withstand an impulse voltage of
This circuit breaker has four poles and provides adjustable thermal and magnetic protection types. It operates within a current range of 400 A and maintains a rated insulation voltage of 1000 V. It ca
The Allen-Bradley/Rockwell Automation 140G MCB series is a series of molded case circuit breakers. According to the National Electrical Manufacturers Association (NEMA), a circuit breaker is a device designed to open and close a circuit by non-automatic means, and to open the circuit automatically at a predetermined overcurrent level without injury to itself when it is properly applied within its rating. The 140G MCB circuit breakers employ different methods to control the operating mechanisms. These methods include stored energy operation, dependent manual/power operation, and independent manual/power operation. When breakers in the 140G MCB family encounter an overcurrent, they can use instantaneous, inverse time delay, and definite time delay overcurrent releases. All these breakers from the Allen-Bradley 140G series of molded-case circuit breakers come with a frame rating of 125 Amps and an interrupting capacity that goes from 25 to 65 kA.
The Allen-Bradley 140G MCB series of circuit breakers are CCC, UL, and CSA certified since they comply with international standards such as the UL, CSA, and IEC standards. Since these circuit breakers have molded cases, they provide short circuit and thermal overcurrent protection by using either mechanical or electronic means. Note that the mechanical means use heater elements to detect the current flow and model the associated heat generated by the current. Additionally, molded case circuit breakers in this family feature either fixed or adjustable trip units. Whether they use fixed or adjustable magnetic and thermal trip units, the motor current rating of these circuit breakers should be less than or equal to 250% of the motor’s full-load ampere rating, or less than or equal to 300% for motors with a current of less than or equal to 100 amperes if the circuit trips on startup. Also, a circuit breaker in the 140G MCB series can be used with a motor current rating of less than 400% for motors with a current rating of more than or equal to 100 Amps if the circuit breaker trips on startup. The safety features of these breakers are capable of preventing accidents such as fires and explosions due to over-current or the overheating of conduits.