2711-T9C10X
The 2711-T9C10X operator terminal boasts a maximum resolution of 640 x 480 pixels. It operates with a power supply of 100–240 VAC and supports communication through DeviceNet and RS-232 printer connec
The Allen Bradley PanelView Standard 900 Graphic Terminals are engineered to suit your needs with excellent graphics capabilities that allow the user interface with their machine. The Terminal features a 9 in. flat-panel display in monochrome, greyscale, or color. These terminals support operator input, through touchscreen, keypad or both touchscreen and keypad. In addition, this HMI comes with a variety of communication port options, adapting to the specific needs of the user.
Browse available units in our catalog of Panelview 900.
The 2711-T9C10X operator terminal boasts a maximum resolution of 640 x 480 pixels. It operates with a power supply of 100–240 VAC and supports communication through DeviceNet and RS-232 printer connec
This operator terminal operates on a 24 VDC power supply and has a memory capacity of 1008 KB. Equipped with a touchscreen input, it communicates via RS-232 while supporting DH-485 networking. Designe
This operator terminal includes a keypad input type and features programmable function keys for enhanced functionality. Operating on 24 VDC, it consumes approximately 70 watts of power. It provides a
The 2711-T9A3X functions as an operator terminal featuring a monochrome display with a resolution of 640 x 480 pixels. This device incorporates both touchscreen and keypad input methods. It is designe
This operator terminal operates with a 9-inch monochrome display and features a resolution of 640 x 480 pixels. It is designed for a touch input experience and supports discrete and block data transfe
This operator terminal boasts a 9-inch display with 384 touch cells arranged in a 24 x 16 formation. It operates within an input voltage range of 85 to 264 VAC, drawing up to 110 VA of power. The touc
This operator interface is equipped with a keypad for input and operates without touch functionality. It includes a DH-485 communication port and a serial RS-232 port for connectivity. The device has
This operator terminal offers a display size of 9 inches and operates at a resolution of 640 x 480 pixels. It features a touchscreen input, supported by 384 touch cells (24 x 16 layout). The device ca
This model includes a keypad with 16 function keys, providing intuitive control options. The terminal supports various communication ports, including DH+ and RS-232 for printer connectivity. It has a
This operator terminal is designed with a monochrome display measuring 9 inches, offering a resolution of 640 x 480 pixels. It supports DH+ networking and includes RS-232 printer communication capabil
The Panelview 900 series is a series of control interface terminals featuring the monochrome and color terminals. The Panelview 900 terminals feature the NEMA Type 12/13,4X enclosures, and they are ideal for indoor use only. The Panelview 900 units are designed with status indicators that are attached to the enclosure. These allow for the monitoring of the Panelview 900 communication status, and they are resourceful in showing the fault statuses. The communication LED turns green to show active communication, while the fault LED turns red to shows that there is a fault, and that troubleshooting is required.
The Panelview 900 terminals feature the keypad and touchscreen input types. The Panelview 900 terminals’ dimensions are 249 millimeters in height, 406 millimeters in width, and 112 millimeters in depth. The PV900M units under the Panelview 900 series feature AC gas plasma screen with pixel resolutions of 640 x 400. The PV900M units feature 384 touch cells with touch cell sizes of 26 x 25 pixels. This series features active-matrix thin-film resistors with cold cathode fluorescent backlights. The Panelview 900 terminals feature an operating temperature range of 0 to 55 degrees Celsius while the storage temperature range is -25 to 70 degrees Celsius. The relative humidity range is 5 to 95%, non-condensing. When installing the Panelview 900 terminals, ensure that the electrical power has been disconnected from the panels. In addition, make sure that the area around the panel is cut out clearly and ensure that metal debris does not enter any of the components installed on the panel. Note that if the installation guidelines are not adhered to, this might result in personal injury or component damage.
If your PanelView 900 fails to startup properly, always check the power supply first. Ensure the terminal is receiving the correct voltage and that the wiring and connections to the power source are valid. In addition, you should also ensure the DC power positive and negative are attached to the proper terminals.
The status indicators are located on the back of your PanelView 900 terminal. The COMM indicator is green and reflects communication. The FAULT indicator is red and reflects hardware faults. Upon startup, the fault indicator should be off and the comm indicator on. If the fault indicator flashes a few times at startup, this is not a concern. However, if both indicators are off you should check the power cable. See the table below to interpret the terminal's indicator status:
| Indicator | Status | Meaning |
| Comm | On | Normal Operation |
| Off |
Fault Present- Ensure controller is in run mode. Check baud settings of controller/terminal. Check for proper controller connections. |
|
| Blinking | Failed to establish communication | |
| Fault | On |
Fault Present - Restart terminal. If the error persists, the terminal requires servicing. Click here for information about DO Supply's repair service. |
| Off | Normal Operation | |
| Blinking | No applications loaded/application is corrupt. Reload the application. |
| Indicator | Status | Meaning |
| Comm | On | Normal operation |
| Off | Hardware failure | |
| Blinking | Failed to establish communication | |
| Fault | On | Hardware failure. |
| Off | Normal operation | |
| Blinking | Application not loaded/application is corrupt |
| Indicator | Status | Meaning |
| Comm | On | Normal operation |
| Off | Communication non-functional | |
| Blinking | Failed to establish communication, PLC may be in program mode | |
| Fault | On |
Fault Present - Check baud rate and rack settings. Ensure proper connections from terminal to controller. Verify remote I/O is enabled. |
| Off | Normal Operation | |
| Blinking | Application not loaded/application is corrupt |
| Issue | Possible Cause | Action |
| Failed Application Download (Initial Attempt) | Disconnected Communication Cable | Check cable type and connection |
| Improper Computer COM Port Selection | Ensure you have the correct COM port number in PanelBuilder32 or WinPFT software | |
| Communication Settings/Rate Incorrect | Ensure computer and terminal share the same communication settings | |
| Failed Application Download (Subsequent Attempts) | Communication Settings/Rate Incorrect | Ensure computer and terminal share the same communication settings. Adjust settings in the Communication Setup screen |
| Application File Name Appears as ******* | Invalid Application | Redownload application |
| Unusable Application Due to Error | Download new application | |
| Failed Application Transfer from Memory Card | Memory card incorrectly installed | Reinstall, verify its installed correctly |
| Application to Large for Terminal Memory | Reduce application size | |
| Incorrect Data Checksum | Ensure memory card is properly seated. It is possible the application may be corrupt | |
| File Format Invalid | Verify file format (.PVA) | |
| Failed Application Transfer to Memory Card | Memory card incorrectly installed | Reinstall, verify its installed correctly |
| Memory Card May be Wire Protected | Change memory card protection switch | |
| Another File on the Memory Card | Erase/reformat card | |
| Application to Large | Reduce application size, erase/reformat card | |
| Memory Card Format Invalid | Replace/reformat card | |
| Incorrect Data Checksum | Ensure card is installed correctly | |
| Application Does Not Exist | Ensure application exists |
Here at DO Supply, we offer repair services for your Allen-Bradley products, such as the Allen-Bradley PanelView 900. For more information or to request a quote, click here.