2711P-B7C1D2X
This operator interface supports a power rating of 70 watts and includes 128 MB of RAM along with 128 MB of non-volatile flash memory. The environmental capabilities allow operation in humid condition
The PanelView Plus 7 series of Allen-Bradley/Rockwell Automation industrial terminals is a series of intuitive and powerful operator interface devices that are certified for usage in hazardous locations. The certifications include the Class I (Div 2), Class II (Div 2), Class III, and ATEX certifications. Also, the series features the NEMA/UL type enclosure protection ratings and these terminals are made to operate at high altitudes and in demanding operating conditions. The PanelView Plus 7 terminals support connection to a single controller and a maximum of 25 screens and 200 alarms. The configuration of the terminals can be performed on the installed Windows CE operating system. Also, the users can access third-party applications and use 2 USB ports that include the USB 2.0 high-speed host port (type A) for removable storage drives and the USB 1.0 high-speed device port for host computers.
The PanelView Plus 7 terminals feature a display size of 4.3 to 5.7 inches (109.2 to 144.7 millimeters) and a viewing area of 95 x 54 or 115 x 86 millimeters. The PanelView Plus 7 terminals have analog-resistive touch input and color TFT LCD screens. The actuation rating of the touchscreens is 1 million presses and they have a maximum operating force of 100 G. In addition to that, the display has a 16:9 or 4:3 aspect ratio, depending on the size of the display. The displays come with backlights with up to 50,000 hours of operating life at medium brightness. The typical brightness of the display is 300 nits and its resolution is 480 x 272 (WQVGA) or 640 x 480 (VGA) pixels. The PanelView Plus 7 terminals have a real-time clock with battery backup. These devices have an operating system memory of 512 megabytes of RAM and 512 megabytes of storage memory. Besides that, the terminals feature 80 megabytes of nonvolatile memory for application storage. The input voltage range of the PanelView Plus 7 terminals is 18 to 30 Volts DC while their power consumption is 25 Watts (maximum).
Browse available units in our catalog of Panelview Plus 700.
This operator interface supports a power rating of 70 watts and includes 128 MB of RAM along with 128 MB of non-volatile flash memory. The environmental capabilities allow operation in humid condition
The 2711P-K7C15D6X operator terminal is equipped with a 6.5-inch color TFT display providing a resolution of 640 x 480 pixels. It supports ControlNet communication ports for integration into complex s
This operator terminal operates on AC input voltage ratings between 85 and 264 volts, while the nominal voltage rating stands at 100-240 volts. The product has a typical power consumption of 20 watts
Designed for interactive control, the 2711P-T7C6D6X operator interface features a vibrant color display that measures 6.5 inches diagonally. The screen supports a resolution of 640 x 480 pixels, provi
This operator terminal supports multiple communication ports, including Ethernet, RS-232, and two USB connections. It operates on a voltage input range of 18 to 32 VDC and has a typical power consumpt
This operator interface operates on a DC input voltage range of 18 to 30 VDC. It offers a power consumption of up to 160 VA for AC and 70 W for DC applications. With a flash and RAM capacity of 256 MB
This operator terminal utilizes a TFT LCD display with a backlight life of at least 50,000 hours. It includes 64 MB of internal memory and is designed for use at an input voltage range of 18-32 VDC. T
This operator terminal operates within an input voltage range of 18 to 32 VDC, supporting a nominal voltage of 24 VDC. It is designed for panel mounting and consumes a typical power of 20 W, making it
This operator interface sports a display size of 6.5 inches, which is characterized by a color format. It operates without touch functionality but retains a keypad for user interaction. The device con
This module runs on a nominal DC input voltage of 24V, with a range from 18 to 32V DC. It also supports an AC input voltage between 85 and 264V. The frequency for operation lies within 47 to 63 Hz. Th
If the PanelView Plus 700 terminal is not starting up correctly always check for adequate power first. Inadequate power can cause a variety of unpredictable behavior. Simply verify the terminal's power requirement in the specifications table. It is also good practice to determine whether there have been any changes since the last startup. Determine what these are to see if they can be reversed.
Battery voltage, as well as the display temperature, are indicative of other potential issues as well. Check the battery voltage and display temperature from the PanelView Plus 700 terminal desktop or from the FactoyTalk View ME station configuration mode. If the voltage is below 2.75 volts DC, consider replacing the battery. Obstructed airflow in the chassis can cause the CPU and/or display to overheat. If the CPU temperature is above 95 degrees Celsius or the display temperature is above 55 degrees Celsius, try to moderate the ambient temperatures.
If you continue have start-up issues, observe the splash screen for state messages and for the status or error codes.
| Message | No. | Meaning |
| RAM Test | 1 | Tests RAM memory |
| Image Search | 2 | Checks for new operating system firmware upgrade on external CompactFlash card and serial port |
| Registry Search | 2.5 |
Locates and loads most recent registry while maintaining multiple copies of the registry |
| Internal CF | 23 | Programs recently downloaded operating system firmware into internal flash memory |
| CRC Check | 24 | Checks operating system firmware integrity |
| Starting System | 28 | Launches the operating system |
| System Check ### | 29 | Checks internal file system integrity |
| System Check | 29.1 | Contact tech support. The internal file system integrity check has been disabled |
| Watchdog Test | 30 | Verifies system integrity by testing watchdog circuitry |
| Stuck Key | 31 | Checks integrity of the function key hardware |
| Stuck Touch | 31.5 | Checks integrity of touch screen hardware |
| Battery Test | 32 | Checks integrity of battery hardware |
| Video Initialized | 37 | Initializes and configures graphic video system |
| External CF | 50 | Transfers new operating system firmware upgrade to the terminal from an external CompactFlash card |
| Message | Error No. | Meaning | Action |
| RAM Test | 1 | Failed RAM Test | Reset the terminal. If the error continues, reset SO-DIMM RAM module. If this does not fix the issue, replace the logic module |
| Internal CF | 23 | Error programming the new OS firmware to internal CompactFlash. | Reload firmware. If the error continues, replace the internal CompactFlash. If this does not fix the issue, replace the logic module |
| CRC Check | 24 | Checksum of the OS firmware failed. | Reload firmware. If the error continues, replace the internal CompactFlash. If this does not fix the issue, replace the logic module |
| Watchdog Test | 30 | Watchdog test failure | Reload firmware. If this does not fix the issue, replace the logic module |
| Stuck Key | 31 | Function key failure | Verify nothing is pressing any keys. Reset the terminal (do not use key presses). If this does not fix the issue, replace the display module |
| Stuck Touch | 31.5 | Touchscreen failure | Verify nothing is pressing the touch screen. Reset the terminal (do not use the touch screen). If this does not fix the issue, replace the display module |
| Battery Test | 32 | Failed battery | Replace the battery. If this does not resolve the issue, replace the logic module |
| NVRAM Access | 33.5 | Nonvolatile memory failure | Upgrade the system firmware |
| EXE Check | 40 | System OS firmware is missing or corrupt. | Reload firmware. If the error continues, replace the internal CompactFlash. If this does not fix the issue, replace the logic module |
| External CF | 50 | Error loading the OS firmware from the external CompactFlash card. | Reload firmware. If the error continues, replace the internal CompactFlash. If this does not fix the issue, replace the logic module |
Status indicators are located on the back of your PanelView 700 terminal. The COMM indicator is green and reflects communication. The FAULT indicator is red and reflects hardware faults. Upon startup, the fault indicator should be off and the comm indicator on. If the fault indicator flashes a few times at startup, this is not a concern. However, if both indicators are off you should check the power cable. See the table below to interpret the terminal's indicator status:
| Fault Indicator (RED) | Comm Indicator (GREEN) | Meaning and Action |
| Possibly Recoverable Error | ||
| Blinking | On | Windows CE Operating System failed or missing. Reload firmware. |
| Off | Most recent firmware download failure. Reload firmware. | |
| Blinking | EBC boot loader firmware missing/failed. Reload firmware. | |
| Fatal Error | ||
| On | Blinking | Fatal display hardware error. Replace display module. |
| Off | Fatal hardware error. Replace logic module. | |
| Issue | Action |
| Dim or Unreadable Display |
Check display settings - When in configuration mode, select Terminal Setting>Display>Display Intensity |
| Backlight Unexpectedly Turning Off or Dimming |
Check screen saver settings - When in configuration mode, select Terminal Settings>Display>Screen Saver |
| Issue | Action |
| Touch Screen Operating Incorrectly/Inaccurate Input and Dragging |
Calibrate Your Touch Screen - When in configuration mode, select Terminal Settings> Touch Screen>Calibration |
| Screen Cursor Not Visible |
Verify the Cursor is Enabled - When in configuration mode, select Terminal Settings> Input Devices> Touch Screen > Cursor |
| Touch Screen Not Accepting Touch Input |
Attach USB Mouse: Mouse works but touch screen does not: Touch driver or screen is nonfunctional Neither mouse nor touch screen working: Application issue |
If the PanelView Plus 700 display lacks a touch screen, you may not have a touch screen display. Check the label on the terminal and the part number of the unit to verify.
Please Note: When calibrating your touch screen, the process requires four (4) screen touches. If the touches are not satisfactory, more will be requested until calibration is successful. If the touch screen does not calibrate or continues to malfunction replace the PanelView Plus 700 display module.
| Issue | Action |
| Mouse Operating Incorrectly | Reattach USB mouse, restart terminal |
| Cursor Not Visible/Mouse Settings Require Adjustment |
Verify the Cursor is Enabled - When in configuration mode, select Terminal Settings>Display>Cursor Check Mouse Settings - When in configuration mode, select Terminal Settings>Input Devices>Mouse |
| Mouse is Composite Device (Keyboard and Mouse) | Replace with standalone mouse |
| USB Mouse Non-Operational | Replace the USB mouse. Current mouse may be noncompliant |
| Issue | Action |
| Keyboard Operating Incorrectly | Reattach the USB keyboard, restart the terminal |
| Keyboard Rejecting Key Input |
Check Keypad Input - If keypad works either the keyboard driver or keyboard stopped working. If neither the keypad nor the keyboard work, an application failure is likely |
| Keyboard is USB Composite Keyboard and Mouse | Simply use a standalone USB keyboard |
| USB Keyboard is Non-Operational | Replace the USB keyboard. Current keyboard may be noncompliant |
| Keyboard Not Enabled |
Check Alt-Ctrl Keys When in configuration mode, select Terminal Settings>Input Devices>Keyboard |
| Issue | Action |
| Keypad Not Accepting Input |
Check Keyboard Input- If the keyboard works either the keypad driver or keypad stopped working. If neither the keypad nor the keyboard work, an application failure is likely |
| Hold-Off Delay too Long/Multiple Key Presses Inhibited by Multi-Key Lockout |
Check Keypad Settings- When in configuration mode, select Terminal Settings>Input Devices>Keypad Note: Home, End, Up and Down keys do not work when single or multi-key lockout is enabled. |
Examine the status indicators at the Ethernet connector. If the indicator is green, a communication link is on. If the indicator is an amber color and flashing, this indicates data activity. You should always ensure there is a good connection to the hub and uplink ports. Poor cable quality and crimping can inhibit the ethernet connection.
When in configuration mode select Terminal Settings> Networks and Communications > Network Connections > Network Adaptors. Check the DHCP. If this is enabled the device will attempt to connect to a valid IP address within seconds of startup. If it fails to acquire and IP address, the TCP/IP protocol will assign 169.254.xxx.xxx. If the DHCP is not enabled, verify the IP address specified does not conflict with another device on the network.
Other devices must not share the same hostname if they are on the same network. When in configuration mode, select Terminal Settings> Communications and Networks> Network Connections> Device Name.
The Ethernet issue may be caused by the other side of the connection.
Here at DO Supply, we offer repair services for your Allen-Bradley products, such as the Allen-Bradley PanelView Plus 700. Click here for more information or to request a quote.