2711P-T9W22D8S-BX
This operator interface operates within an ambient temperature range of 0 to 55 degrees Celsius and supports storage temperatures from -25 to 70 degrees Celsius. The viewing area measures 196 x 118 mi
The Allen Bradley Panelview Plus 7 is an Operator Interface Terminal which has a display size ranging from 4 inches to 10 inches. They use WIndows CE 6.0 and can be programmed with Factory Talk View Machine Edition. These terminals are capable of monitoring an application remotely using a VNC connection. This module includes 512 MB of Ram and uses an SD card to copy and restore the operator interface.
Browse available units in our catalog of Panelview Plus 7.
This operator interface operates within an ambient temperature range of 0 to 55 degrees Celsius and supports storage temperatures from -25 to 70 degrees Celsius. The viewing area measures 196 x 118 mi
The 2711P-B7C22A9P-BX is an operator interface designed for effective interaction in various applications. It operates within a voltage range of 100 to 240 VAC and has a compact display size of 6.5 in
This operator interface includes 80 MB of free user memory and has no physical keypad, relying solely on touch input. It is designed with a 15-inch display, providing a visual area of 381 mm, and supp
This operator interface includes a 15-inch display with a resolution of 1,024 x 768 pixels and a brightness level of 300 cd/m². The device operates on a DC input voltage of 24 volts. It features dual
This operator terminal provides an analog resistive touchscreen with an actuation capacity of 1 million presses, requiring a force of 100 g. It encompasses 512 MB of RAM and an additional 512 MB of no
This operator interface supports an input voltage range of 100 to 240 Volts AC and operates with a power consumption of 105 volt-amperes. The display boasts a brightness rating of 300 candela per squa
This operator interface features a display with a resolution of 1,024 x 768 pixels and provides an operating temperature range of 0 to 55°C. The viewing area measures 304 x 228 mm. This model consumes
This device supports a viewing area of 376 x 301 millimeters and is suitable for ambient operating temperatures from 0 to 55°C. Its thin film transistor (TFT) color LCD has a typical brightness of 300
The operator interface boasts a display size of 15 inches with an aspect ratio of 4:3. Its touchscreen is rated for 1,000,000 presses, making it durable for extensive use. The ambient operating temper
This operator interface device operates in ambient temperatures ranging from 0 to 55°C in non-condensing environments. It features a high-resolution display of 640 x 480 pixels (VGA) with a typical br
Two status indicators are located on the back of your PanelView Plus 7 terminal. The STS indicator is green and communicates that the terminal is powered on and operating. The ERR indicator is red and communicates hardware and or firmware faults. Upon starting your terminal, both indicators will initially flash, and the STS indicator will continue to flash as startup progresses. If the indicators do not turn on, always check the power cable. Once the startup has completed successfully, the STS indicator remains on. See the table below if the terminal stops during the startup process:
| ERR Indicator (Red) | STS Indicator (Green) | Meaning/Action |
| Possibly Recoverable Error | ||
| Blinking | Off | Firmware error. Redownload firmware. |
| Failed configuration. Restore factory default image. | ||
| Fatal Error | ||
| On | Blinking | Display hardware error. Replace the terminal. |
| On | Hardware error. Replace the terminal. | |
If your PanelView Plus 7 terminal fails to startup, always check for adequate power first. Verify the terminal's DC power requirements are being met. Startup failures can also be caused by incorrect wiring. Review the wire specifications for your terminal and verify that the DC power wiring is correct. Check the status indicators. See the table above. Ensure noting is touching the display during startup, as this may cause startup errors. Finally, ensure the progress indicator has not stalled. If it has stalled, reload the firmware or restore the terminal to factory default settings.
If your PanelView Plus 7 terminal is restarting for seemingly no reason, first check for incorrect wiring. Review the wire specifications for your terminal and verify the DC power wiring is correct. Intermittent terminal restarts can also be caused by the processor overheating. Check the processor temperature, the operating temperature, and review the System Event log for over-temperature conditions. Also, verify that there is adequate clearance around the terminal.
| Issue | Action |
| Temperatures Beyond Operating Range | Check the Monitors tab to review temperatures. Normal operation will not resume until the system has cooled to a normal operating temperature. |
| Low Display Brightness |
Adjust the Brightness Setting - Select Terminal Settings> Display> Display Intensity Use the arrows to change the intensity and press Enter to save |
| Low Screen Saver Brightness |
Adjust the Screen Saver Setting - Select Terminal Settings> Display> Screen Saver Use the arrows to adjust the intensity and press Enter to save |
| Issue | Action |
| Touchscreen Nonfunctional | Verify the touchscreen is not damaged. If it is, the terminal must be replaced |
| Incorrect Calibration | Recalibrate the touchscreen |
| Touching Multiple Input Points | The touchscreen does not support multiple operations simultaneously. Ensure you do not touch multiple input elements at once and that you do not rest your hand on the display. |
| Issue | Action |
| Cable Connections are Poor | Verify network connections and check the status indicators. The green indicator will turn on when a link has been established and the yellow indicator will blink when activity is detected. |
| Invalid Ethernet Connection | Ensure there is a good connection to the hub and uplink ports. Poor cable quality and crimping can inhibit the ethernet connection. |
|
Invalid IP Address |
Check the DHCP. If this is enabled the device will attempt to connect to a valid IP address within seconds of startup. If it fails to acquire and IP address, the TCP/IP protocol will assign 169.254.xxx.xxx. |
| Conflicting IP Addresses | Check the DHCP. If the DHCP is not enabled, verify the IP address specified does not conflict with another device on the network. |
Here at DO Supply, we offer repair services for your Allen-Bradley products, such as the Allen-Bradley PanelView Plus 7. Click here for more information or to request a quote