2711P-T15C22A9P-BX
This operator interface offers a viewing area measuring 304 x 228 mm and operates optimally at ambient temperatures between 0 and 55°C. The unit's storage temperature tolerance ranges from -25 to 70°C
The Allen Bradley Panelview Plus 7 is an Operator Interface Terminal which has a display size ranging from 4 inches to 10 inches. They use WIndows CE 6.0 and can be programmed with Factory Talk View Machine Edition. These terminals are capable of monitoring an application remotely using a VNC connection. This module includes 512 MB of Ram and uses an SD card to copy and restore the operator interface.
Browse available units in our catalog of Panelview Plus 7.
This operator interface offers a viewing area measuring 304 x 228 mm and operates optimally at ambient temperatures between 0 and 55°C. The unit's storage temperature tolerance ranges from -25 to 70°C
Designed for use in non-condensing environments, the 2711P-T10C22D9P-BX operates within an ambient temperature range of 0 to 55 °C. It has a maximum power consumption of 32 to 50 watts. The touch scre
This operator interface operates within an ambient temperature range of 0 to 55°C, and can withstand storage temperatures from -25 to 70°C. The unit has a typical brightness of 300 candela per square
This operator interface operates on a 24 Volt DC input voltage and consumes a maximum power of 50 watts. Its touch input facilitates easy user interaction. The display boasts a 4:3 aspect ratio and ma
This performance terminal has a color active matrix TFT LCD display, providing a resolution of 640 x 480 VGA with 18-bit color graphics. The terminal features an application memory of 1GB, along with
This operator interface offers a display resolution of 800 x 600 pixels with a 4:3 aspect ratio. It operates on a rated supply voltage of 85 to 265 Volts AC and has an input voltage rating of 24 Volts
Designed for effective operator interaction, the 2711P-T12W21D8S-BX supports a rated supply voltage between 85 and 265 Volts AC and can operate with a 24 Volts DC input. It has a memory capacity of 51
This operator interface features a 12.1-inch display offering a resolution of 1280 x 800 pixels. The unit operates effectively at an input voltage of 24 Volts DC and consumes a maximum of 50 Watts. Th
This unit features a display area of 376 x 301 mm (14.8 x 11.9 inches) and operates with an input voltage that ranges from 100 to 240 VAC. It includes dual Ethernet ports and three USB host ports for
In the realm of control systems, the 2711P-RP7AMX logic module stands out with features like a maximum Ethernet cable distance of 100 meters (328 feet) and compatibility with SODIMM RAM. The device is
Two status indicators are located on the back of your PanelView Plus 7 terminal. The STS indicator is green and communicates that the terminal is powered on and operating. The ERR indicator is red and communicates hardware and or firmware faults. Upon starting your terminal, both indicators will initially flash, and the STS indicator will continue to flash as startup progresses. If the indicators do not turn on, always check the power cable. Once the startup has completed successfully, the STS indicator remains on. See the table below if the terminal stops during the startup process:
| ERR Indicator (Red) | STS Indicator (Green) | Meaning/Action |
| Possibly Recoverable Error | ||
| Blinking | Off | Firmware error. Redownload firmware. |
| Failed configuration. Restore factory default image. | ||
| Fatal Error | ||
| On | Blinking | Display hardware error. Replace the terminal. |
| On | Hardware error. Replace the terminal. | |
If your PanelView Plus 7 terminal fails to startup, always check for adequate power first. Verify the terminal's DC power requirements are being met. Startup failures can also be caused by incorrect wiring. Review the wire specifications for your terminal and verify that the DC power wiring is correct. Check the status indicators. See the table above. Ensure noting is touching the display during startup, as this may cause startup errors. Finally, ensure the progress indicator has not stalled. If it has stalled, reload the firmware or restore the terminal to factory default settings.
If your PanelView Plus 7 terminal is restarting for seemingly no reason, first check for incorrect wiring. Review the wire specifications for your terminal and verify the DC power wiring is correct. Intermittent terminal restarts can also be caused by the processor overheating. Check the processor temperature, the operating temperature, and review the System Event log for over-temperature conditions. Also, verify that there is adequate clearance around the terminal.
| Issue | Action |
| Temperatures Beyond Operating Range | Check the Monitors tab to review temperatures. Normal operation will not resume until the system has cooled to a normal operating temperature. |
| Low Display Brightness |
Adjust the Brightness Setting - Select Terminal Settings> Display> Display Intensity Use the arrows to change the intensity and press Enter to save |
| Low Screen Saver Brightness |
Adjust the Screen Saver Setting - Select Terminal Settings> Display> Screen Saver Use the arrows to adjust the intensity and press Enter to save |
| Issue | Action |
| Touchscreen Nonfunctional | Verify the touchscreen is not damaged. If it is, the terminal must be replaced |
| Incorrect Calibration | Recalibrate the touchscreen |
| Touching Multiple Input Points | The touchscreen does not support multiple operations simultaneously. Ensure you do not touch multiple input elements at once and that you do not rest your hand on the display. |
| Issue | Action |
| Cable Connections are Poor | Verify network connections and check the status indicators. The green indicator will turn on when a link has been established and the yellow indicator will blink when activity is detected. |
| Invalid Ethernet Connection | Ensure there is a good connection to the hub and uplink ports. Poor cable quality and crimping can inhibit the ethernet connection. |
|
Invalid IP Address |
Check the DHCP. If this is enabled the device will attempt to connect to a valid IP address within seconds of startup. If it fails to acquire and IP address, the TCP/IP protocol will assign 169.254.xxx.xxx. |
| Conflicting IP Addresses | Check the DHCP. If the DHCP is not enabled, verify the IP address specified does not conflict with another device on the network. |